Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Pls say , how we calculate lux / sq.ft, which formula used
for calculation

Answer Posted / krishna pathak

To Calculate the no. of fittings in a room,
the formula is
N=No. of Light fittings required= A x E/(Lxuxd.f)
.'. E= N x (Lxuxd.f)/A
where L=> Lumen o/p
A=> Area (m^2)
E=> Illumination or Lux levels (in lux)
u=> coefficient of utilization
d.f=> Depreciation Factor
For Detail study refer Philips,G.E(lighting)& Artlite
Catalogues.

Is This Answer Correct ?    24 Yes 9 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

If i am running of spindle at 2000rpm ,but How to spindle stop at the second I am resetting the machine in CNC machines

1624


how to find ratio of CT & PT in 66/11kv 12 mva supply system ? explain with calculation.

2388


WHAT IS SHORT CIRCUIT STRENGTH OF 100 AMPS MCCB?

2101


how to prepare the technical test

2070


What should be the magnetic balance test values for a 3 phase delta/star connected single primary dual secondary winding transformer (90 MVA / 2 X 45 MVA TRANSFORMER)

1898


i need of the bhel question papers along with answers and also give some website names for the downloading question (electrical and electronics engg question)please help me....

1893


Why Neutral Isolation is required?

2213


How DC earth leakage currents can be reduced ?

1916


L.A. (Lightening Arrester) is located at a place from where transmission line enters the transmitting substation. So L.A. (Lightening Arrester) is the first equipments which has to encounter with lightening, high voltage surges and switching surges. It has to absorb energy of lightening, high voltage surges, and switching surges. L.A. (Lightening Arrester) is made up of layers of semiconductors. If these layers can not tolerate energy released by lightening, high voltage surges, and switching surges the L.A. (Lightening Arrester) blasts.

1088


There are different classes of protections in power plants.class a,b,c are clear..is there any class d and e r there..and elaborate class b protection.

2078


how ct burden,magnetising current,ratio and knee point voltage are related & derived

2187


Advantages/Disadvantages of earthing of neutral bus on MSB instead of separate neutral earthing for transformer/DG sets feeding to MSB

2777


What are the classifications of oscillators?

1066


What is servo motor? what is its purpose?

2037


HELLO EVERYONE, I RECENTLY HAVE FOUND ONE PROBLEM, I WAS TAKING NO LOAD TRIAL OF AN HT MOTOR 920 MOTOR , 1440 RPM , 6.6 KV, WITH AUTO TRANSFORMER. AT 450 V, LOAD WAS 40 AMP AND SPEED WAS 250 RPM. BUT AS WE INCREASE VOLTAGE FROM 450 TO 480V, LOAD BECOME 41 AND SPEED REDUCED TO SOME RPM . SO WHICH PHENOMENON ACTED HERE FOR REDUCING SPEED.?? AND IS IT HAPPENING ALWAYS OR IT IS RARE? I ALSO HAVE FACED SUCH PROBLEM WITH FEW LT MOTOR ALSO.

1940