HOW DO YOU PROVE THE HIGH VOLTAGE CABLES OR BUSBAR IS DEAD
EVEN AFTER IT IS DE ENERGISED
Answer Posted / rod
As we are dealing with high voltage it is critical that the
correct procedure is used. 1/ A switching sheet should be
used to ensure that both sides of the test point is
isolated locked and tagged, 2/ A Modiwak (HV sensor) should
then be tested on a known live source first then the
isolated point should be tested and the Modiwak should then
be retested on the known live source, this ensures that the
Modiwak is functional, 3/ Then dressed in the correct PPE
earths may be installed, making sure the the earths are of
a size for the fault level at that point.
All the previous answers are partly correct but to prevent
accidents it is esential that a strict procedure is used.
| Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
What are the causes of unbalanced current on 34.5kv feeder Ia=0.05,Ib= 0.25, Ic=0.15 and In=0.27 prior to tripping current are balance?
impliment (AB)`+C to transistor representation
What is the resistance of the field winding of a d.c. Shunt generator kept low?
plz send me the syllabus or any sample paper for engineer trainee recruitment if any,on ravinder911@yahoo.com
what are the factors to be considered while design the breaker either HT or LT??
What is the accepted limit to increase the choosen transformer capacity over the load and why ?
Which type of transformer is used for lighting loads?
How Can You Relate Power Engineering With Electrical Engineering?
What is the dc grounding system and what is diff between AC/DC grounding system?
we use capister for power factor. when we use capaciter in dg circuit than defect dg. can we use capaciter bank for dg circuit
explain the process of commutation in a dc machine. Explain what are inter-poles and why they are required in a dc machine.
What is Percentage impedence of a transformer? why it is expressed at a percentage? what is the importance of percentage impedence in case of a transformer?
How to calculate pitch, gauge of winding wire, and No. of turns for 30HP, 3 phase, 4 poles 50Hz, 380V induction motors
Why Water motor is not taking a load or pressure while everything is correct. (Note: Motor running properly)
What is meant by reactance voltage?