Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

We have 250 KVAR cacitor bank & our average load is 200kva
but our power factor is average 0.66 how can we maintane
it? how can we balance our load?

Answer Posted / joseph

It is better to express the `Load' in kW. In your case it
is assumed that the average load at a P.F. of 0.66 is about
132 kW. Please note that excessive capacitors in circuit
can act as `Load'. Hence, firstly ascertain whether the
Power Factor is 0.66 lag (lesser capacitors than required)
or 0.66 lead (more capacitors than required). The best way
is to switch off all the capacitors for some time and take
the P.F., kW, KVA readings from your meter. Based on this
suitable solution can be provided.

Is This Answer Correct ?    9 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What happens when ac supply is given as excitation voltage instead of dc supply

3895


A 3 phase transformer's (Y-Y) Y and B phase is (Y and B connection not broken) broken from neutral and R and Nutral connection is ok, what will be the relay tripping and why

2011


Capacitor is load free component but why ampere meter shows current when capacitor bank breaker close?

1240


What is a differential amplifier?

1324


Atwhat condition reverse power relay will act?

2297


Electronic circuit

1091


How can we calculate the efficiency of a Running (On-Load) Motor ? What parameters are required and what is the method ?

2036


define as synchronous generator

2216


What is Annunciation?

2100


how to decide no of electrodes for 1600A LT Main incomer panel

1704


use of choke in APFC panels

5920


if main CT is of ratio 50/5, and meter CT is -/5 what will be overall multiplying factor of meter.PT is 11000/110 .

1711


what is the criteria for selection of conductor used for ehv ac electrical dischrge

2157


WHat is the general checks required for Dry type transformers

2129


We have 90mX100m hangar with 16 no.of supporting pillar. It is required to provide power supply on all pillars. what is suggested earthing scheme for hangars.

2057