can we load Power capicitors on DG sets?
Answer Posted / reshi
Not at all ,Since DG sets are already generating the rated
voltage required and the designed power factor. For the
sake of discussion if we agree to install the capacitor on
DG sets it will give rise to the overvoltage and the
nearest downstream equipments are most probably not safe by
this option of having the capacitor on the DG sets.
Capacitors are required when the power factor is required
to improve and the best practice is it shall be installed
as close possible to the load.
| Is This Answer Correct ? | 5 Yes | 1 No |
Post New Answer View All Answers
how can tell us the AC indoor or outdoor which Tr and formulls
What is the function of the generator exciter?
How to know about the rating(voltage and other) of induction motor if its name plate is missing at the manufacturing site.
What is the practical way to calculate the cable size for known ampere load?
please send me last 5 year interview questions
What is ST and specify its range of voltage.
i have some screw comprressor with 630kw power,i have established them with simple star to delta circuit,by the way there is so much inertia when the screw comprressors start, can you offer me contactors power with 400vac or any cataluge to choose the contactors
Do closed loops systems require manual input?
What does the term power factor shows?
how to find number of run cable laying[LT side] for transformer & alternator secondary side? [above condition for getting output power transformer to main panel side] give the example.
Define relative stability.
What the difference between ac and dc inductor an capacitor
explain which quantities change in the starting and the and the running condition in induction motor
how give earthing conection to household equipment?
What is Control & Relay Panel? And Remote Control Center?