why 4-20 mA signal is preferred over a 0-10V signal
Answer Posted / banibrata
In case of voltage transmission(here 0-10V)
1.there will be voltage drop along the transmission wire.
2.if we use 0 volt then we will be unable to find whether
the obtained 0 volt output is really the system output or
its due to instrument error.So for "live zero" concept we
need to give a particular value(other than zero) in the
lower range value.
3.Capacitive and magnetic effect due to voltage
transmission will be more than that in case of current
transmission.
4.2-wire transmission is not compatible with voltage
transmission.
But in case of 4-20 mA signal the above problems are solved.
1.In series transmission same current flows through the
ckt.So no current drop occurs.
2.Here the lower range value is 4 mA.So we can easily
detect after looking at the o/p whether the instrument
error occurs or not.In case of instrument error zero
reading will be shown.
3.2-wire transmission is compatible with it.
| Is This Answer Correct ? | 52 Yes | 5 No |
Post New Answer View All Answers
I want to know about DDCMIS in detail ? please explain it. Also give name of reference books in which it is explained in detail in very simple manner.
line up procedure for dp type flow transmitter?
I will attend an interview with GasGas company for a position of Instrument Technician ( Offshore )in next month can anyone tell me what questions they will ask. Thanks in advance.
why we r opening HOT BYPASS valve during startup of a compressor?
what is the procedure for auto tune in masoneialn 12300 series displacer type transmitter?
how 3 out of 2 Logic/interlocks works? give brief explanation with help of diagram.
can anyone can let me know in Eurotron Micro cal 2+ calibrator in milli amps source mode we are not able to get 20 milli amps output it only produces 1.52 milli amps out, but display shows increase in milli amps , and err6 displays, let me know how to remove the err 6.
Isometric drawings are generated during _________________ phase of a project
What are the interlocks we have to check during the start up of LP/HP compressor?
What is instrumentation measurement?
how is work pressure switch& level switch?what is the principle of this?
What is standard of DCS panel design?and what is step of DCS panel design?wiring and type of connector(screw or DB connector)
What are the type of bonnets in the control valves?
why we use cascade control and feed foreword control in 3 element control of boiler drum ?what is feed forward and cascade control system ?
What is the difference between ff transmitter and non ff transmitter