I HAVE CONSUMER WHOSE POWER FACTOR IS 65% I WANT TO INCREASE
IT TO 98%.HOW TO CARRY OUT?
Answer Posted / mubashar ali
you can calculate VRAr, those required for improvment 0.65
to 0.98
KW(Tan1-Tan2)
KW= your total load
Tan1= cos invers of first pf ,than take tan1
Tan2= cos invers of second pf, than take tan2
then u find total KVAr reqird , and installed same rating
capictor
Is This Answer Correct ? | 12 Yes | 0 No |
Post New Answer View All Answers
how the works electronic energy meter?
how to wiring it with contactor and timer together
how harmonics generated in induction furnance? how minimise it?
what is dc mator?types of dc motor?losses in dc motor?what is the mechanical,electrical and commercial efficiency of a dc motor?
What is the use for cable entry in control room?
what are the effects when a salient pole alternator is run at high speed like 3000 r.p.m?
Why r u using pf panel. what the uses
What is the principal of motor?
How Load Factor, Demand Factor, Diversity Factor etc best applied in designing an electrical circuit? Is it allowed to consider these factors in each and every panel in an electrical distribution system? Can any body suggest a good book for reference?
magnetizer priciple
why dimmerstate always connected in star connection? what will happen if it connected in delta?
what is the path of thunderlightening? once both a buffalo and a person were standing 5m apart but lightening hit and killed buffalo not person?
What is creepage distance..... what will be the value for different voltage level
how to select battery for 15 KVA UPS with formula
what are the applications of transistors with low dc gain, high dc gain and medium dc gain( beta)?