I HAVE CONSUMER WHOSE POWER FACTOR IS 65% I WANT TO INCREASE
IT TO 98%.HOW TO CARRY OUT?
Answer Posted / mubashar ali
you can calculate VRAr, those required for improvment 0.65
to 0.98
KW(Tan1-Tan2)
KW= your total load
Tan1= cos invers of first pf ,than take tan1
Tan2= cos invers of second pf, than take tan2
then u find total KVAr reqird , and installed same rating
capictor
| Is This Answer Correct ? | 12 Yes | 0 No |
Post New Answer View All Answers
What must be the minimum distance maintained between 2 Generators as per International standards?
In power transmission using open belts or horizontal shafts it is preferable to have the slack side of the belt on the top because
Briefly describe your ideal job?
Why does inductive loads consume KVARs?
we have require a Motor (1500kW, 6.6kV, 50Hz) which shall operate at 1500rpm during 30min and after it shall run on 500rpm during 15min. The same cycle shall be repetitive during the whole working days. Which method is best and economic to achieve such type of task. VFD, VVFD, Pole changing motor etc.
What is FM200 Gas??Applications........
How to decide no. of Step and Kvar for APFC Panel 40 kvar MD: 33.12 KVA Avg pf : 0.8540
Consider three heater bank connected in 3 phase star with neutral.Each heater bank connected in each phase.So each phase get 230 volts supply.my question is,during balance condition, current flow in neutral or Not
What does quality factor depend on in resonance?
what is the difference between active power and reactive power and apparant power in practical as well as theoritical
armature is that part in which current is induced since in dc motor we supply current to the conductor so why we call it armature?
What is the working principle of CFL & T5 tube light & 40W tube light with electronic ballast?
Explain the fundamental difference between emf (electro motive force) and pd (potential difference) ?
we have a rewind motor of 2Hp,2800Rpm, 220Volt AC. how can we choose the running capacitor for this motor, any formula for that?
why T/F winding temp measurement cts are odd secondary current ie,109A/1.2A/1.4A?