6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?

Answer Posted / rvg

The transformer details shows no load voltage and we can
assume about 3-4% decrease with full load. ACB with rated
voltage 690 should not be suitable for 725V. ACB's nominal
voltage should be 1.414 time the applied voltage.

Is This Answer Correct ?    6 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

In the formula : Knee point voltage = Burden X alf / class, Please inform what is alf? regards Shashidhar M.R.

3391


I Need standard operation procedure(SOP)for 500kva Oil type transformer oil filtration & Procedure for IR value checking.

2362


how to calculate the conductor size for certain KV transmission line and distribution line?

2005


what is meant by carrier aided trip protection in transmission line

3304


State Maximum Power Transfer theorem.

720






Both generator parallel condition shared load equally but one genrator taking ampere more than the other what are all the causes to make like this

1240


how could we calculate the no of outgoings from a 800 watt distribution board

1253


what happen as when voltage drop(or may decrease) ? in case of atomic base theory?

1537


why core is useful for a transformer ?and also in its operation ?

1574


Transformer diagram mention each parts ?

1578


Why earthing is necessary for any equipment?

1163


Is better to supply the voltage for static exciter from the auxiliary power source or from the SG terminals? And why?

1486


How to calculate capacitor bank value to maintain unity power factor with some suitable example?

661


how we arrange the hv side with delta connection in case 33/11kv of transformer.

1535


What is the role of power pack in substation protection system?

2221