6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?
Answer Posted / rvg
The transformer details shows no load voltage and we can
assume about 3-4% decrease with full load. ACB with rated
voltage 690 should not be suitable for 725V. ACB's nominal
voltage should be 1.414 time the applied voltage.
| Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
how can we phase identification in a distribution line,how we recognise that which phase is coming for a house hold connection.help me............
3phase motor can be used as a Prime mover for alternator.
how does directional relay work incase of ac ?
How will you utilise electrical power? You can start from the generating station.
what is the necessity of under ground cables ??
how to calculate the size of the HT cable
please suggest some good universities with low cost iam in totally full confusion so please help me my profile gre 283 and ielts 5.5
how to find the voltage's of a transmission line plzz help with pictures i am not able to understand
When lag/lead/lag-lead compensation is employed?
Do u know any one? how to find out in motor rated amps? formula?
On what basis the the size of Lightning arrester for buildings are selected ?
i have some screw comprressor with 630kw power,i have established them with simple star to delta circuit,by the way there is so much inertia when the screw comprressors start, can you offer me contactors power with 400vac or any cataluge to choose the contactors
Explain Active power,reactive power,how its related to each other , & inductive ,capacitive.
Why ground terminal is used in pot meter 10k ohms
pls,send the previous year written test questions.