why is the vector group analysis done in transformer tests
Answer Posted / joe callaghan
Transformer vector relationship is tested by shorting the
primary A phase to secondary A phase, then applyying a
three phase voltage to the primary side of the transformer.
Voltage measurements are then taken as follows:
A-B
B-C
C-A
B-b
C-b
B-c
C-c
These values will then allow you to draw the vector diagram
of the transformer.
| Is This Answer Correct ? | 32 Yes | 9 No |
Post New Answer View All Answers
Is it possible to make a 5P10/ CT Ratio 50/1A Burden 5VA
from where the self excitrd induction generator get the power?why is the voltage regulation is poor of seig?
what is th basic difference between a d latch time line and a d flip flop time line???
can mini-curcuit supply MIL-tested transformer !
can any one know is sbi interview based on merit or based on roll number
what is mean by NPS (Negative phase sequence)fault? what is the difference between EFR & OCR faults?
To make a basic instrumentation amplifier, it takes A One op-amp with a certain feedback arrangement B Two op-amp and seven resistors C Three op-amps and seven capacitors D Three op-amps and seven resistors
Electromagnetic torque developed by the motor is compared to shaft torque. A less B same C depends on motor design D more
when we decide to use soft starter drive or vfd drive in mcc to operate apump?
how does it help for selection of a transformer.
What is the function of NER and NET?
What is the method for testing the differential protection stabilty in generator? When the time of starting What will happen if differentail protection connection wrong means?
Is it required to lay 2 runs of GI wires along with armoured cables from one power DB Machines of higher rating?
relation between power station capacity and voltage level?
How to Calculate The Neutral Earth flat design calculation for the Synchronised generator (Gen 1-650Kva, Gen 2-725Kva