Answer Posted / s.madhavan
The answer above is partially correct. All AC alternators
presently manufactured are brush less type with built in
AVRs ( Automatic Voltage regultors ) Normally AVR get feed
back from load for its regulation. If the loads connected
have excessive harmonic content, feed back to AVR get
distorted and hence regulation gets affected. To avoid this
a PMG is mounted on the alternator itself which feed DC to
armature winding without reference to the load
| Is This Answer Correct ? | 31 Yes | 15 No |
Post New Answer View All Answers
with help of neat sketch explain principle of TIG welding process
What is the need for a controller?
How to calculate earth fault current for 6.6 KV , 50 HZ , 756 Amps , 3000 RPM , 0.8 PF generator
is there any lightning by passer is arranged in ship like buildings?
Phase control and integral control are used for?
hi friends if you have any 400KV Substation Erection and installations Drgs please send to me.My email id:kandi.suresh441@gmail.com
What is the application of Dyn1 and Dyn11 vector group of transformer?
IN induction motor pf is increased using capacitors.what will be the effect on motor and system when very large capacitor is accidently installed and pf goes leading.
What is essential to prove safe isolation of electrical circuit?
can anyone show me how the 3 phase power is supplied to socket outlets?
if we run a 3 phase machine on two phase what will happend??? given answer with solid reason please
What is relation between mu(nought) and epsilon(nought)?
what are the standard IR values should be of R-E, Y-E, B-E, R-Y, Y-B, B-R of VCB in closed condition and in open condition for 500KVA & 1000KVA transformers. and what is the acceptable range when tested by 5000V megger.
What Is Connection APFC Panel In Compony.
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?