I have installed capacitor bank at secondary transformer.
cos phi is increase. but on load (far from transormer), it
still poor. Can anybody explain it??
Answer Posted / jinu
capacitor bank will improve the power factor towards the
supply side only. ie if you are measuring the power factor
before the capacitor bank it will show the improved power
factor. But the same time when you measure it after the
bank it will show you the load power factor not the
improved power factor.
| Is This Answer Correct ? | 19 Yes | 0 No |
Post New Answer View All Answers
Don't you have similar question banks related to Oral Certification Examination conducted by Mercantile Marine Departments / Directorate of Shipping, Ministry of Shipping for Electro Technical Officer?
How to design the NGR Resistance
what is meant by impulse voltage?
What is dc current source? Differentiate between ideal and non ideal current sources?
how to calculate the loss tangent of electrical cables
why fractional pitch winding generally used in alternators?
Star Delta Diagram with full description
I have 2500KVA transformer delta/star,13.8KV/380V provided with LV 4000A breaker. Already I have 2300KW motor feeder with a full load 90%. Is it possible to connect another 1600A from that breaker? If so how the calculation is done?
How to calculate Voltage regulation of 22 KV Over head Line.
pls tell what are doing the three phase motor star and delta connetion with circuit diagram and control wiring .
Is there any Electrical supervisor license which gives permit to work whole India rather than individual state??
how can we find thae value of capacitor for single phase motor. what is difference between starting capacitor and running capacitor.
what is the reactance,capacitance & impedence electrical armoured & unarmored Cables.
How many types of electric motors are there?
When we use 3 terminal resistor?