Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

RATING OF LIGHTENING ARRESTER FOR 11 KV LINE IS 9 KV BUT WE
KNOW THAT LIGHTENING ARRESTER IS USED FOR OVER VOLTAGE
PROTECTION SO WHY NOT THE RATING OF LIGHTENING ARRESTER BE
MORE THAN 11KV ???????????????//

Answer Posted / nageshwar

FOR A 11KV LINE LINE TO GROUND VOLTAGE IS 11KV/SQRT(3). IT
GIVES OF THE ORDER OF 6KV ONLY. AS ARRESTER IS USED FOR
LINE TO GROUND TO DISCHARGE THE FAULT CURRENT TO GROUND ITS
RATING SHOULD BE MORE THAN 6KV. GENERALLY WE USE 9KV.

Is This Answer Correct ?    32 Yes 16 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

i want use the cable size 16cx4 core aluminium usege watts 240x2000w this cable size is correct?

2201


how to calculate kvar in Akiva

1937


Explain cos(theta) and Sin(theta)

2102


What is the formula to calculate the rating of a three phase air circuit breaker

2322


Compare jfet’s and mosfet’s.

1284


What is meant by rotor?

1274


how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?

2455


how tto ingress mw in turbine explain.procedure ?

2302


WHAT IS THE WINDING PROCEDURE OF ELECTRICAL MOTOR

3976


Actuality I have at home electrical panel with 220v 50hz, and I want to converter from there to 110v 60hz, to wiring on the half of my house. Also I like to keep another half of my house with the original 220v 50hz. What is the best and safety way to do?

1815


CAN WE CALCULATE THE NEGATIVE SEQUENCE AND ZERO SEQUENCE REACTANCE OF A GENERATOR USING ONLY ITS RATED VOLTAGE, KW, PF AND SYNCHRONOUS REACTANCE??? IF YES, THEN HOW??

5637


What is the transfer function?

1080


why transformer tank is in rectangular shape what happen when it is in step shape

1450


why the starting voltage drop in a cable needs to be limited?what is percentage of the voltage drop allowed during starting?

1811


Is any generator is developed which is operated with out diesal or other expensive source?

2106