why 4-20 mA signal is preferred over a 0-10V signal
Answer Posted / supratim samanta
If 0-10 mA is used instead of 4-20mA then there will be
difficulties in error detection.Such as if there is any
fault is the transmission lines..we will never know,wheather
the indicated 0mA current corresponds to the initial
value(calibrated) of the measurement or it is due to fault
in transmission lines.
| Is This Answer Correct ? | 120 Yes | 24 No |
Post New Answer View All Answers
what are the values of fuel flow rate in various places in boiler.
How would you choose differential range?
what is the minimum power (P=VI)to produce a spark?
How INtools is useful for routine Instrument maintenance?
Which is the best field foundation bus. ( FF ) Yokogawa, Honeywell or others ?
OBJECTIVE TYPE QUESTIONS OF ANALYTICAL INSTRUMENTATION
What is PDS and PDMS ?
I want to buy a seal kit of a pneumatic power cylinder.But I don't know it's specification.So please help me to know its specification.
There are many type of control cable like pair,core,tried, What are defination each one
What is cut off relay? And why use in PLC and DCS?
What is the difference between conductive lined pipe and conductive unlined pipe? Why do we see that?
KAlman filter code for two dimension?
what is metal of piston ring
how to connect transmitter measuring sulfur process? 1-by using long impulse line or 2- by using coated short impulse line
i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....