plz tell me about for how many rating (for 500kva)how much
current taken?

Answer Posted / kapil

what is .8 doing in the above formula, while the rating is
given in the KVA and not in Kwatt.

the formula is ..KVA=1.732x Volt x Amp
where voltage will be taken as 415 volt. which is very
common in 3 phase motor rating.
this will produce the same answer as above [695 amps]

Is This Answer Correct ?    27 Yes 12 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

which protection used in power plant?

1502


how to minimize earth resistance upto 2Ω, if the resistance is 6 Ω ?

1450


How to select the cable and voltage drop in circuit?

1179


how r charge carriers produced

1628


Can you please explain creepage distance in detail, for a 6.6kV cable head what must the distance be and how do you determine it?

2334






Give accurate definitions for these electric terms: Inductor Inductance Inductive Induction Reactance Reactive Esam Baraka ٢١ ساعة

914


why swityard is necessrry requirement in any bis power distributin systems?

1885


Hi friends, i m electrical engineer i want a cdr for migration purpose so anybody have information about this then send me on jayesh_ee88@yahoo.com.please try to me

1430


Define the overload capacity of the motor?

1579


what is transformor oil gread

1966


Why derivative controller is not used in control systems?

650


hi, i have 3x200KVA and 2 x 80KVA UPS with battery bank of 150AH 68Nos. and 100AH 204Nos., i need to install AC either ductable or PAC type, so can you help me to calculate heat load and capacity of the AC to install.

2333


What is touch potential and step potential?

1626


HELLO EVERYONE, I RECENTLY HAVE FOUND ONE PROBLEM, I WAS TAKING NO LOAD TRIAL OF AN HT MOTOR 920 MOTOR , 1440 RPM , 6.6 KV, WITH AUTO TRANSFORMER. AT 450 V, LOAD WAS 40 AMP AND SPEED WAS 250 RPM. BUT AS WE INCREASE VOLTAGE FROM 450 TO 480V, LOAD BECOME 41 AND SPEED REDUCED TO SOME RPM . SO WHICH PHENOMENON ACTED HERE FOR REDUCING SPEED.?? AND IS IT HAPPENING ALWAYS OR IT IS RARE? I ALSO HAVE FACED SUCH PROBLEM WITH FEW LT MOTOR ALSO.

1450


what will be d.g. capacity to cater together for 14hp A.C. load & 3kw lighting load

1549