What are the various methods for effecive earthing in a
factory in a rocky terrain, where soil resistivity is
extraordinarily high? The usual method of 3 m deep earth
pits is not serving the purpose.
Answer Posted / blake australia
There are some powders which harden (i.e. erico make some I
think). Generally would drill a fairly deep hole. insert
earthing rod and surround with these earthing enhancers.
Try to avoid gell or powder forms of earth enhancer as they
tend to wash away when it rains
| Is This Answer Correct ? | 7 Yes | 4 No |
Post New Answer View All Answers
If 22 KV HT line, Current transformer is 25/5 then how to calculate multiplying factor.
What is nyquist contour?
What should be the amps for a MV fuses for transformer 630kVA 20(10)/0.4 kV
Different STANDARDS (BS, IS, IEC etc) gives different informations on CT specification. How they correspons w r t each other (i.e I mean to say BS provides "knee point voltage" but IS does not, then how can i select CT)
how much allowable resistance that can be difference in motor all coils?
In case of generator when we consume more power produces by it why load on generator increase and starts sound more. and how it is adjusted..
Where can I get CPWD electrical specifications & Shedule of rates? Please help me
What is the effect of atmospheric pressure & Temp; on efficiency of motor? Why NGR(Neutral Grounding Resistor) is used in 132/11 KV Transformer & how? What is the use of Auto T/F in Grid Station?
As i want some model question paper in basic computer science and history please send me immediately sir
Type of motor stater detail and working detail
why voltage form factor of PT are increase , when it is ecpected heigher spikes in system. how it is calculated.
3- What is the target from Zero Impedance, Single Phase Imp., S/C Imp. and magnetic balance tests?
is it possible to start a motor in felid connected to a remote mcc
In the formula : Knee point voltage = Burden X alf / class, Please inform what is alf? regards Shashidhar M.R.
Is it required to lay 2 runs of GI wires along with armoured cables from one power DB Machines of higher rating?