What is mean CT Saturation? How to calculate?
Answer Posted / jai sherring
CT saturates if it is not correcly rated. its ratio has to
be matched to the maximum fault current that it has to
pass. normally the ratio of fault current to rated current
should be kept within 20.
it is very relevant that the fault current is calculated as
per the upstream network fault level. furthe the X/R ratio
of the connecting network needs to be known for calculating
the DC component and its time delay. if the time constant
is small, the saturation shall occur for the first few
cycles, and delaying the actuation will solve the initial
mis-read of current signal. but if the time constant is
large, say of the order of ten cycles, proper sampling
solutions have to be resorted to, that is the current must
be sampled before the onset of saturation.
| Is This Answer Correct ? | 55 Yes | 34 No |
Post New Answer View All Answers
Is there a diode made that works with AC 120 volt 20 amp? If so can it completely stop all current flow in 1 direction at all times?
I have motor of 3 H.P. How i found the rating of capacitor use in it in single phase motor..???
how to select the mpcbs and contactor for 3 phase 30 hp star delta motors.for plc control.and tell me the calaculation for future use.
Define the three phase formula fuse.
An automatic water heater is an example of which type of control system?
WHAT IS AIR GAP VALUE IN MM FOR A 11KV BUSHING OF 11KV/440V DISTRIBUTION TRANSFORMER. AND AIR GAP VALUE OF 25 KV BUSHING OF AT TRANSFORMER OF 25 KV TRACTION. WHAT IS THE CALCULATION FOR THE AIR GAP PERMITTED FOR BUSHINGS AT DIFFERENT VOLTAGES.
How to select cable the size, what is the parameters use and what is the formulas use for this cable size calculation?
In a large office how do we calculate required number of light fittings, assuming fittings are 4x18W or 2x36W fluorescent fitting ?
What is open delta Xformer? It's adavntages & Use?
lamination figures
why impedance relay is used for medium transmission line protection
bitumar
What happen to generator if i have unbalanced load?
what are the tests comes under the type test, what tests comes under routine tests.
How to determine alternating current frequency?