CONSIDER A 415V/200V STEP DOWN TRANSFORMER.CAN WE USE USE
IT AS STEP UP TRANSFORMER BY GIVING 200V IN SECONDARY AND
TAKING OUTPUT FROM PRIMARY?
Answer Posted / akialok
during the design of power transformer,or any distribution
tfr the load current is taken into account ,and the windings
of the secondary side are accordingly designed that is the
load currents it can sustain ,insulation and cooling system
are taken into consideration...
suppose in your designing u r designed the windings to
sustain a 30 amp load current while reversing the windings
and taking the out put from primary as u stated, the load
current will be decreased at the 415 voltage side and the
current in the 220 voltage ll be increased to a factor of
transformation ratio as it has to work in same power..so the
windings of the 220 side may burnt out..if its not capable
of sustaining the increased current.
| Is This Answer Correct ? | 25 Yes | 6 No |
Post New Answer View All Answers
How can I calculate ISF of current transformer?
Which motor is 3.3 or 11kV more reliable, in terms of efficeancy,maintenance, reliability.
Make a list observation on Transformer?
What is highest size of HT motor like 11 kv or 33 kv,and how to make it 750 rpm.i think the size will be very big.any idea ? pl. reply..
WHAT IS THE USE OF PIG TAIL IN WINDOW CT ?
HOW TO CALCULATE HV TEST VOLTAGE FOR ELECTRICAL EQPT.
what is the relationship between phase & neutral
what is the pre charge circuit,what will be work which function it will be use plz tell me
What is the function of NER and NET?
while starting a liquid starter ,is there any volage drop on water/soda on tank.can we touch the tank on starting?
lenz law application and define
How many types are using in 220kv/400 kv swith yard
what is Fan Control Cubicle
can any one know is sbi interview based on merit or based on roll number
what is transistors comprised of?