CONSIDER A 415V/200V STEP DOWN TRANSFORMER.CAN WE USE USE
IT AS STEP UP TRANSFORMER BY GIVING 200V IN SECONDARY AND
TAKING OUTPUT FROM PRIMARY?

Answer Posted / akialok

during the design of power transformer,or any distribution
tfr the load current is taken into account ,and the windings
of the secondary side are accordingly designed that is the
load currents it can sustain ,insulation and cooling system
are taken into consideration...
suppose in your designing u r designed the windings to
sustain a 30 amp load current while reversing the windings
and taking the out put from primary as u stated, the load
current will be decreased at the 415 voltage side and the
current in the 220 voltage ll be increased to a factor of
transformation ratio as it has to work in same power..so the
windings of the 220 side may burnt out..if its not capable
of sustaining the increased current.

Is This Answer Correct ?    25 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What magnetic circuit is formed in berry-type constructions and why?

656


What are the factors which influence the choice of specific magnetic and electric loadings of a synchronous machine?

1595


What is the kiosk parts, about them and their functions ? If anybody have some PDFs files or details about this plz send it on tawhidfaisal@Yahoo.com

1398


What is speed mode?

1251


In single phase ac ups supply when current is measured with tong tester neutral current is found more than phase current.What is the reason?

1604






is oil viscosity affect on motor current?

1511


What is the difference between earth fault protection of motor feeder with CBCT and Without CBCT ?

2288


CAN CU XLPE/PVC CABLE BE USED INPLACE OF LOW NOISE SCREENED CABLE? KINDLY GIVE REASONS

1410


What is resonant frequency?

704


What is the effect of pd controller on system performance?

643


what is the physical connection of a analog i/p to a analog i/p module (ab plc)and through a analog o/p module(ab plc) to a analog o/p . and how all the process control by scada

1439


TO CALCULATE THE RESISTANCE OF GRR OF HT MOTOR 400KW WHEREAS STATOR VOLTAGE 6.6KV AND ROTOR VOLTAGE 705V AND ROTOR CURRENT IS 346A.

4943


difine electrical ballast in HPSVL

1559


what are the Alarm, Trip & Safety equipment (Issues) present in Power Transformers pls Mail it to ashokbabunhce@gmail.com

1451


What Is HO factor in power selection

1559