hw to calculate flc of motor ? data are:3-phase,50Hz,30kw
Answer Posted / chetan & panks
Please mention voltage level & PF.
Assuming the voltage level 415V & PF 0.85,
FLC=kw/(ROOT3xkVxcoso)
= 30/(1.74x0.415x0.85)
= 48.87A
| Is This Answer Correct ? | 52 Yes | 4 No |
Post New Answer View All Answers
What are factors to be considered while we selecting the Core Balance Current Transformer for Earth fault protection
how a flip flop can be used as a latch?
Is there any problem about which the drive (inverter) doesn't show/display the alarm and/or fault but instead of this , it doesn't work ? I want to know that could there be any kind of problem in the drive when the drive doesn't display the alarm and/or fault ?
in parallel operation of power transformer why the distance between power transformer and capacitor bank feeder is necessary to know
During underground cabling in landscape area what did we cover the cable with to prevent the electric shock & protect the cable?
What are the basic component of a cro?
What is the maximum percentage voltage drop (vd%)for a motor control center
how to select size of hardware for linking aluminium busbar is it depend on area of busbar or current flowing through bus bar
draw the restricted earth fault protection circuit install on power transformer and identify its parameters and draw C/C curve of it
what is effect of leading power facter on the system and billing
when will be the iocl interview results i faced interview on 8th september 2008 iam from electrical branch i faced interview for the post of electrical engineer??????????????????????//
What is inverse definite minimum time lag relay? Where is it use?
what is diff. between earthing grid,earthing mess, earting grid?
how you configure motorvision relay (L&T make)from DCS
Make a list observation on Transformer?