Passive Flitering-
An LC circuit, tuned to each harmonic order to be filtered, is installed in parallel with the non-linear load. This bypass circuit absorbs the harmonics, thus avoiding their flow in the distribution network.
Generally speaking, the passive filter(LC series ckt in parallel with Non linear load ) is tuned to a harmonic order close to the order to be eliminated. Several parallel-connected branches of Passive filters can be used if a significant reduction in the distortion of a number of harmonic orders is required. It offers both power-factor correction and high current-filtering capacity .Passive filters also reduce the harmonic voltages in installations where the supply voltage is disturbed. If the level of reactive power supplied is high, it is advised to turn off the passive filter at times when the percent load is low.
AHC Active harmonics filter-
AHC comprising power electronics and can be installed in series or parallel with the non-linear load, compensate the harmonic current or voltage drawn by the load. A parallel-connected active harmonic conditioner (AHC) compensating the harmonic current (Iharm = -Iactiv) by injecting Iactiv in opposite phase.
The AHC injects in opposite phase active current the harmonics drawn by the non-linear load, such that the line current Is remains sinusoidal.
Hybrid Filtering (Combined Active & Passive Filter)
Passive and active filters are combined in a single system to constitute a hybrid filter. This new filtering solution offers the advantages of both types of filters and covers a wide range of power and performance levels.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is meant by control system?
how to produsing geretor power
whate is the meaning of balance/unbalance,in stabilizers type
what happened when we supply a dc current in dc motor?? can it worked properly?
why generator efficiency is more in swinburnes test?
What is stacking factor? What is its approximate value?
what questions are asked in the interview for the post of an electrical maintenance engineer in FMCG companies?
How generator NPS(NEGATIVE PHASE SEQUENCE TEST)TEST WAS DONE? PROCEDURE WITH DETAILS?
what happen when power factor of 2 parallely operated transformer become equle?
what are the 4 rules to start the motor?
how to operate and maintenance of 1500 kva diesel generator set
How to know any size of cable if there are not written on cable? Answer must be theurical not by experience.
What happens to voltage when current is zero?
When we use air circuit breaker, it has O/L protection ,time delay SC protection, Instataneous SC protection & ground fault protection. They all have some setting range. But what is the suitable/allowable setting for the above protection which will be safe for the equipment? For example-O/L protection setting have a range of (0.4,0.45,0.5,0.55,0.6,0.65,0.7,0.8,0.9,1.0)xIn Time delay SC protection have a range of (1.25,1.5,2,3,4,6,8,10,12)xIn Time delay setting is 0.02,0.1,0.2,0.3,0.4 Instataneous setting is fixed to 20xIn Gound fault setting is given 100A,300A,600A,900A,1200A This setting are for 2500A ACB. So what will be the basic allowable setting for the above protection? is there any formulae to calculate this<
State magnitude criterion.