What is the calculating formula for HT and LT amps in a
transformer.
Answer Posted / siddhartha tyagi
IF 2500 KVA T/F , 11KV, 433 VOLT
APPARANT POWER(VA) = 1.732.V.I
H.T SIDE CURRENT = 2500*1000/1.73*11*1000= 131.21 A
L.T SIDE CURRENT = 2500*1000/1.732*433= 3333.52 A
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
How much inductance or resistance require as a starter in series with induction motor of specific capacity(e.g. 5 hp) ? What is formula for it ?
i have 3500 amp load and select current transformer and perches.how i calculate .please understand
use of PIR in ehv breaker
If a 3 phase induction motor is in off condition in the conveyor and rotor of the motor keeps moving with the conveyor than the resistance of windings of motor varies. why is it so ??
What is the difference between security constraint unit commitment and security constraint optimal power flow?
What is Faraday's law
How the setting of the vector surge relay shall be calculated when the relay is to be used for Grid islanding application?
how was your last weekend.
how to handle 2500 kva transformar
In synchronization circuit what is the function of Interposing voltage transformer(IVT)and Reverse voltage transformer(RVT)
What are the conditions to be satisfied for parallel operation of dc generators?
what is the use of permanent magnet generator in exciter
how many parameters can integrate with fire alarm basically ?
I have a current transformer with 1 main reading meter with transformer outside the building and a control panel having 5 CT reading meters with black round coils inside the building. I want to know, A) when current pass through the Transformers, will the current be reduced or be the same and after that B) when current pass through the CT meters with black round coils, will the current be reduced or be the same. C) in the above process will the reading of the main meter be same or different, from the total reading of all the 5 CT meters.
star delta starter contorl circuit... drawing..