If the load of transformer is getting more than its
rating,,,than how to overcome this problem? Suppose thee
rating of transformer is 315kva and the load is going
beyond than the rating say around load: 352kva...
Than how can we solve this problem without deducting the
load.
Answer Posted / kumar
Imagine 352 kva load operating at the pf of 0.8. If you're increasing the power factor to 0.95 by using static or synchronous capacitor the the kva will reduce to 274 kva and the transformer now meet the demand comfortably
Apart from this the other method is to connect another transformer in parallel with the existing one
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
WHAT IS IM (INDEX OF MOUNTING )IN MOTORS
IN SINGLE PH TRANSFORMER IF LEKAGE IMPEDANCE DROP IS NEGLECTED ,THE FLUX IN THE MAGNETIC CORE and the lekage flux linking a winding are a)proportional to the applied v to the winding i respectively.
What does ampere turns shows?
Earth bits close or open. Which is correct
What shall be the secondary output voltage if the primary winding of a 220/6V, 50 Hz transformer is energized by an 110V, 60 Hz supply?
10 Mtr Hight of Lighting Arrestar how much area coverd??
What is I to C?
Explain what is electric traction?
What is power factor why we should maintain the power factor unless what will happen
why wire sizes are 3/29 or 7/29 and why not wire sizes are 2/29 or 6/29?
what is the difference between switchgear and circuit breakers and is there any difference between outdoor and indoor switchgear and circuit breakers , and how would you differentiate between switch yard and substation and grid station . thanks
In what condition the HT fuse breakes?
What is the ratio of Booster transformer?
please send 5yearje solved papers on my email himmatsinghnathawat@gmail.com
How to decide CT & PT ratings for a given transmission line carrying some rated voltage?