what is the difference between LPF and UPF wattmeter and
where it is used.
Answer Posted / nitish kennedy
Low Power Factor wattmeters are specially designed to measure power at low power factor .
Ordinary wattmeters (i.e. UPF) are not accurate in measuring power at low power factor beacuse of -
low deflecting torque.
error due to inductance of of pressure coil is large at low power factor.
So some modifications are done in LPF wattmeters-
low value of pressure coil resistance to increase the torque.
pressure coil current is compensated using compensating coil.
capacitor is connected in pressure coil to reduce the error due to pressure coil inductance.
control torque is made very small.
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
Can you any one explain application of buccholz relay operation and pressure relif device operation of power transformer
State magnitude criterion.
Is Transol transformer oil comparable to nynas nytro libra?
in science exhibition how lamp can blink when you clap near the lamp ? thank you
1) What are your personal strength? 2) What are your personal areas of improvement? 3) What are your expectations from from a particular job? 4) what are your carrier objectives?
Define phase lag and phase lead?
if we run a 3 phase machine on two phase what will happend??? given answer with solid reason please
my name is venkat .i have good percentage in my academics(ssc 86, intermediate 83 b.tech 73) my question 1..after completion of my ssc i joined in bpc but i didnt got rank in emcet so i completed MPC in one year compartmentally ..so here what am expect question from this background?
is it necessary to earth the rmu before cutting off the transformer winding?if yes why?
what are the things that can cause a three phase motor to crawl?
How to calculate cable size by using load.?? Any formula...
Whether 3 phase induction motorwith 100 hp capacity , Amp 160 for which sensitive earth fault relay , type CTUM 15 can be used?
Why it is necessary to isolate fire fighting when you are taking shutdown for lv board.
how to find number of run cable laying[LT side] for transformer & alternator secondary side? [above condition for getting output power transformer to main panel side] give the example.
How can we calculate the motor frame sizes?