2 electric bulbs of 100w,200V are put in series & the
combination of each bulb is supplied to 100 V . the power
consumption of each bulb will be????????
Answer Posted / mudasar marwat
R=V^2/P = 200^2/100 = 400 ohm
power consumed by each bulb is calculated by the same expression
P=V^2/R
but here the voltage is equally divided between two bulb which is 50 now across each
so P=50^2/400 =6.25 w
| Is This Answer Correct ? | 24 Yes | 4 No |
Post New Answer View All Answers
why the frequency and voltage in india is 230v and 50HZ. when compared to USA say 110v and 60 HZ.
A 100KVA SINGLE PHASE TRANSFORMER 10000/200V,50HZ REQUIRES 300V AT HV SIDE TO CIRCULATE FULL LOAD CURRENT WITH LV SHORT CIRCUITED.THE INTAKE IS 1000W.THE % OF REGULATION ON FULL LOAD AT 0.8 PF LAGGING WILL BE HOW MUCH AND THE SECONDARY TERMINAL VOLTAGE ON 0.8 PF LEADING WILL BE
please tell me when we start motor without load in star or delta connection whose current above condition,pl write formula
How many types are using in 220kv/400 kv swith yard
How to select the earthing transformer,for DELTA TO DELTA TRANSFORMER OR ALTERNATOR SIDE.Pls post your answers and calculation.
How much no load current of synchronous motor
what is thermal resistance of PVC Cable.
i have attended the interview on 4th June,08 at Kolkata in IOCL, can anybody tell me what is its result
How to calculate total harmonic distortion level(THD) in VFD? and how can we reduce harmonics?
following are the questions asked in interviews: 1) Considering the short circuit fault, which switchgear is preferable, SFU OR MCCB? Which operates faster? whicg one is popular in Indian Market and why? 2)Define SCPD. What is type2 coodination? 3)Why the contactor rating is higher for the fuseless selection than for fuse selection? whether the ratinf of SFU or MCCB remains the same in both the cases? 4)If the HP rating is known then can you calculate the ratings of L.V Switchgear(SFU/MCCB, contactor, OLR) without using the selection chart?
What is a parabolic signal?
Why IR value of the (HT cable Plus synchronous motor) is less while individually having IR values in GΩ?
Differentiate between Zero and Negative sequence current
How much pf maintan in dg set in 6o% load,when Dg runnig Neutaal Earthing removed what happen.
TRANSFORMERS WITH DC SUPPLY