How to calculate VCB current rating for 2000 KVA transformer
Answer Posted / k. kannan
Power=1.732*415*I
I =2000000/1.732*415
I=2782.5 amps
Vcb =I=2000000/1.732*11000
I=104.97 amps=I=105 A
Suitable VCB 125 AMPS
| Is This Answer Correct ? | 7 Yes | 16 No |