Why we using 250ohm resistance during lab calibration and why not using in field in one plz define deeply???
Answer Posted / vibhash kumar(voith)
Because our maximum electronic components working in the range of 1 to 5 VDC.250 omhs is suitable for the both 1 to 5 V and 4 to 20 MA.through the omhs law.if we will take 4mA it will for 1vdc and 20 mA for 5 vdc( V= IR).we are not using in field because AI 250 mA already contains.so we have no need in field.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
what is cems analyzer explain with principle and drawing ?
why micro controller 8051/52's clock frequency is internally divide by 12 ?? and why it is further divide by 32 in UART serial communication ??
please send the drdo exam paper
What are primary elements of measuring pressure?
god evening sir i am studying m.sc(tech)electronics &instrumention.am i elegible to all industies
What is mean by analytical instrumentation?
What is standard of DCS panel design?and what is step of DCS panel design?wiring and type of connector(screw or DB connector)
How vortex sensor used for steam flow measurment can be checked on line i.e without taking out from process line.
why I need valve guard and whats different between guard and positioner ??
What are advantages and disadvantage of the ac supply load cell?
Explain the working principle of lvdt?
What is the purpose of the analyzer in petrochemical plant?
Which is the best field foundation bus. ( FF ) Yokogawa, Honeywell or others ?
Any body have know try work calculation ???
how can be calibrate flow indication transmitter (rosemount) it shows excess milli amps nearly about 24 ma on full scale, but its scale was set on 20ma on full scale..???how can be simiulate..???