I have 30 kw motor load & i have selected 10 kvar capacitor bank for power factor improvement.my existing p.f is 0.85 & proposed p.f is 0.99 so ,is it right selection?
2 nd question how to connect c.bank whether in delta or star connection & how to decide it?
Answer Posted / bhaskarenterprises1
as per electrical calculations if we want maintained .99 pf we should have 14.31KVAR is sufficient.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What’s electric traction?
Formulae for calculating the transmission line losses for different voltage levels
what is magnetizing current test in power transformer
I need bhel previous year quetion papers for electrical engineering department.I searched but i could not find out
which capacity of RCCB used for five thousand watt electricity load?
why do we put a transformer on soak before loading it
what is the purpose of high speed earth switch in gas insulated substat
IN SINGLE PH TRANSFORMER IF LEKAGE IMPEDANCE DROP IS NEGLECTED ,THE FLUX IN THE MAGNETIC CORE and the lekage flux linking a winding are a)proportional to the applied v to the winding i respectively.
What is the difference between the transmission line and distribution line?
can i use ups power as a raw power for another ups
in 132kv substation CRT means
Diagram on interconnectivity of 11kv transformer with RMU (i.e, one incoming and two outgoing or two incoming and one outgoing)
what is magnetizing and demagnetizing current in generator and motor?
FOR 16/20 MVA 132/33 KV ONAN/ONAF TYPE TRANSFORMER IT IS DESIGNED FOR 16 MVA WITH ONAN CONDITION.IT BECOMES 20 MVA UNDER ONAF CONDITION.LOAD LOSS IS GUARANTEED FOR 65KW AT 20 MVA AND % IMPEDANCE 13.75. PLEASE TELL US AT WHAT LOAD LOSS AND % IMPEDANCE IT SHOULD BE DESIGNED FOR 16 MVA AND WHAT WILL BE ITS EFFICIENCY AT 20 MVA?
any one please tell taht what type questions will be asked in BHEL interview, i am having interview on 24th Dec, please send this to mail pradeepsistam@yahoo.co.in