Answer Posted / ranjith
In Mahesh's answer, it says 'Nodes are I/O communication protocols' this part is wrong.
In a typical DCS architecture from top you have got,
0. MES/SAP/
1. Operator station
2. Runtime/Database/Historian/Batch/Gateway & Engineering Servers
3. Controller
4. IO nodes
5. Marshalling Panel
6. ...(I'll stop here)
The IOs are generally not clustered with the Controllers, IOs will be in a different panel communicating with the controller in various communication protocols(exceptions are there).
There will be a slave module communicating to the master(Controller) and also communicating to the IOs connected to its Backplane/Bus of the slave. This slave module and the IOs are collectively called as 'Node'.
There will be multiple nodes due to segregation of IOs(Plant/unit/Process part) or to distribute the slave module's load (different manufacturer has different IO density specified or may be limitation of protocol).
Now imagine wiring the whole bunch of field signal cables to your control room...!
An alternative is to take a communication cable from 'Main control Room/Center' to 'Remote/Sub station' may be kilometers apart and enjoy limited wiring.
Total number of nodes are limited by the communication protocols itself. (Payload, Noise, Cycle Time ...)
Further reading:
Industrial Communication Protocols /Fieldbus
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
Why mmwc unit is used?
what is the calibration procedure for magnetic flow meter @ onsite
Q- Control problem are mainly classified in _____ types. a-)4 b-)3 c-)6 d-)nono of these Few of them i know is 1- regulator type problem (eg- Air conditioner) 2- tracking problem (eg missile trcking problem) 3- sybernatics 4- optimal control problem
how to calculate range of level transmitter?
why use 50% lel methane gas concentration for gas detector calibration instead of 60% lel gas concentration whereas the hi alarm set at 60% lel.
i am having information technology branh ....... can i prepare for psu exam
what is 24vdc live and dry supply
I have 0.75mm sq multicore cable (IS type) , can use instead of same type but 1.5 sq mm cable ? Note : The distance is around about 150 meter.
With N nodes and B branches what will have a network ???
please can any one tell me clearly about pid tuning i am confusing about this .how to tune pid easly?
Draw symbols of the following :
how to convert cubic metre per hour to newton cubic metre per hour
Somebody can explain me about >Critical Loops, calibrations, ESD critical Loop checks, Logic Diagram / Cause & Effect checks for ESD loops,
Operational amplifiers
How to calibrate H2s Dectector