I have 12MW gas engine based power plant its running parallel
with grid. my problem is When cpp run in island mode(without
geb) that time geb transformer power factor is 0.2 lagging.
When cpp run with parallel that time power factor is 0.94 lagging
So how can i maintain power factor ofgeb transformer in island
mode 0.9 lagging?
Answer Posted / perladelsur
I had been involved in similar scenary in a 1500 MT/D chamical plant where we operated in synchonized normal operation mode condition but in case of public electrical system disturbance due to severity storn, we were about to go into the islaned mode operation.
What we did was, to install an automatic power factor control (APFC) bank to put an end at this problem so we reach o.96 PF during islaned operation.
Bye
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
How to calculate Ith (I thermal) for curent transformer
What is the cut-off rate?
how can we design robots
Write a note on materials used as a fuse element.
How does cost of generation from hydropower plant compare with other sources of electricity?
H.t motor 6600 volt to same motor lt supply 440volt supply applyed to h.t motor to effect....
what r the safety measures in UPS ? explain all?
What is VCB? where it is installed at SP. What is SP?
What are the necessary components of the feedback control system?
what is effect of 5amp fuse on 2mva pry protection of transformer
If one tertiary phase i.e. R,Y or B is earthed of a loaded type tertiary delta connected (Without load)of a power auto transformer, what is its advantage/disadvantage?
Mention the methods for starting an induction motor?
please send me previose rrb junior engineer qustion papers
how does this job compare with others you have aplied for?
What is the maximum breakdown voltage of 11KVA and 66 KVA power line and how it is calculated?