How much Resistance Show by RTD(PT100) when it is installed in process(Consider Process Fluid temp 29 Deg C)?
Answer Posted / ashwin patel
111 ohm as,
Rt=R0(1+αt), where α=0. 00385, R0=at 0°=100ohm resistance for PT100,
Rt=100(1+(0.00385*29))
Rt=100(1+0.11)
Rt=100*1.11
Rt=111ohm
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
How is PH sensor works ?
Hi, I am Newely Joined in Construction company instrument engineer? Any one can Plz tell me How can I advanced preparation for Releated Engineering and construction Documents?
how to calculate signal cable sizing? and multipair cable sizing??explain in brief?
What are the types of control valves available
where i can get training in INTOOLS and PDMS in Delhi-NCR OR north part of India. please reply with ur ans. at arunsamkaria@ymail.com
how many types of preheaters are in cement industry & what r they can any body explain?
wich is coming the first HAZOP OR SIL
Senior engineer's please help me, what is Loop Checking and Loop test? and write difference also? soon urgent
What care will you take in the installation of control valves,SCADA,DCS and FOC in Oil and Gas Project?
What is standard procedure of manual mapping in Radar type level transmitter?
What is the difference between ff transmitter and non ff transmitter
how will you check torque value during Factory acceptance Test for control valve/ESD ON/OFF VALE how will you confirm this torque value is being correct, Which document will you be refer.
Why mmwc unit is used?
How to calibrate the flow transmitter
Why use ball valves on Gas pipelines instead of gate & or globe valves...means basic diffrence or use of these valves..how designers knows this type of valve with rating is required...