Is it possible to interlock between ACB & MCCB?
Answer Posted / g.pattabiraman
For positive, fail safe interlocking, between ACB and MCCB to prevent both getting ON at any given time,
use of UNDER VOLTAGE COIL, along with auxiliary switches of the breakers is needed
ACB under voltage coil in series with MCCB aux. N.C contact
and MCCB under volt coil in series with ACB aux. N.C contact will give this fail safe protection
Motor operation or manual operation are user choice
Is This Answer Correct ? | 4 Yes | 0 No |