Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Could explain briefly of over excitation in transformer.

Answer Posted / mayur kavar

The transformer works on the principle of mutual induction between the primary and secondary windings. The induction is caused by the constantly varying magnetic flux that links the two windings. The flux density in the windings is directly proportional to the induced voltage and inversely proportional to the frequency and the number of turns in the winding.

Magnetic Flux α Voltage/Frequency

Overfluxing is a dangerous situation in which the magnetic flux density increases to extremely high levels. The high flux density can induce excessive eddy currents in the windings and in other conductive parts inside the transformers. The heat generated by these eddy currents can damage the windings and the insulation. The high flux density also causes magnetostriction inside the transformer core and produces noise. The powerful magnetostrictive forces can also cause damage. The winding temperatures may also increase due to the heat produced.

The magnetic flux density is dependent on the current flowing through the primary windings in a transformer. This current is dependent on the voltage applied across the windings and the winding impedance. The impedance is dependent on the frequency of the applied voltage. If the nominal voltage is applied at a reduced frequency, the low inductive reactance will cause a higher current to flow through the windings.

Overfluxing is usually encountered in Transformers which are directly connected to the generator. It usually occurs when the generator is being started or stopped. As the rpm of the generator and consequently the frequency of the power falls, the same system voltage induces a higher magnetic flux. Modern Automatic Voltage regulators are equipped with V/Hz limiters which limit the voltage in accordance with the frequency.

Overfluxing can be prevented by the use of a Overfluxing relay. An overfluxing is an adaptation of an overvoltage relay. The PT voltage is connected across a resistor and a capacitor in series. The voltage sensing relay is connected across the capacitor. The relay operates in the event of an overfluxing and isolates the transformer

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why do we use 25kv supply for traction purpose?

1924


how to check ac servo motor

2275


What is the criteria that generally follow by distribution licenses to fix contact demand of their industrial customers?

1523


How to find ampere on ht side for selection of cable size ???

1802


sir my exam is on 19/6/2013 under electrical branch pls send me sample aptitude questions as well as sample technical questions for jindal steel and power company

2278


i m electrical diploma holder i want to do plc $ Scada some body tell me which insitute is best for me near chandigarh

3106


what is the criterion for selecting vector group of Transformers ? i mean how to decide vector group of Generator transformer, substation trasformer and transformer at consumer end

2361


how to estimate wiring ins roughing ins. and boxes

2400


A 15 kw squirrel cage motor having a maximum efficiency of 90% on a continuous full load has temperature rise of 42 degrees celcius after 30 min and 52 degrees celcius after 1 hr under the above operation conditions. a) calculate its final steady state temperature rise on continuous load and the heating time constatnt. b) if the motor is operated on a short load for 9 min estimate its temperature rise. c) calculate the maximum overload that can be applied on a short, 9 min rating so that the temperature rise is the same as the final steady state temperature rise on continuous load.

1111


how can i improve the power factor in domestic (230v)

2065


HI SIR, AM PREPARING FOR RRB FOR SECTION ENGINEER POST. PLZ SEND ME THE PREVIOUS QUESTION PAPERS AND HELP ME. I HAVE NO ENOUGH TIME MY EXAM DATE IS 22ND JUNE.... MY EMAIL ID IS nalla.amarnath@gmail.com

1943


State the formula for overall efficiency of thermal power station

3047


difference between high and low impedance BUS BAR relay??

1621


if the number of poles generated in stator and rotor side of an induction motor are different then what will happen and why?

1887


Can we use BS 6651 and BS EN 62305 standards for computer room lightning ptotection in substation?

2257