15hp,380v,31amp,3-ph submersible motor run at 250v what is
The temperature rise of submersible motor

Answer Posted / shubha_ee

If motor is fed from Delta connected supply.....
P=15hp = 11.19kW
so P per phase = 11.19/3 = 3.73kW..
pf = 11190/(1.732*380*31) = 0.55(lag)
then Vp=VL = 380V..
and
Ip=IL/1.732 = 31/1.732 = 17.9Amp..
So, R per phase = (380)^2/P = (380)^2/3730 = 38.71 ohm..
so, Heat dissipation for 1sec due to I^2R loss,
H1 = (17.9)^2*38.71*1 = 12403.07 Joules...

Now, if the VL=250V = Vp then IL= 11190/(1.732*250*0.55) = 46.98Amp...
so, Ip=46.98/1.732 = 27.12Amp...
So, Heat dissipation due to I^2R loss for 1sec ,
H2 = (27.12)^2*38.71*1 = 28470.98 Joules...

Now, increase in heat dissipation = (H2 - H1) = 16067.91 Joules
so, increase in temperature is 8.46 deg Celcius.....(as 1degC = 1899.1005 Joules)

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Dear sir my name Ankit i m Diploma holder present working in Welspun Corp ltd Anjar as Asst.engg (salary 14400/month ctc) i Would like to change my company also i have selected in ford India pvt ltd Sanand as trainee Tech with salary 12000/month so please suggest me for changing my job hope for *ve response

2421


What is a fuse? How does it work? What are materials used?

1528


What is the use for cable entry in control room?

708


Hi Suppose we have a wye/wye transformer which is grounded at both sides,in this situation, do we have ay ground transformer? in other words, ground transformer can do any thing more (while we have nuetral wire in both sides)? As the last question, what about 3rd harmonic? we have two choices: first using wye/delta transformer + ground transformer and second using wye/wye earthed connection.in the former choice, we dont have 3rd harmoonic at the secondary side but what about Yn/yn conection? do we suffer from 3rd harmonic in the Yn/yn connection?

1523


Is it posible to instal one more SMDB from the existing SMDB and is it practical.

1596






what is the difference between neutral and earth

1554


How to calibrate or test an LT Air Circuit breaker 440 volts, 35 KA, 800 Amps ?

1508


I am shobana from Chennai. I am having my personal interview on 19th Dec at Chennai.kindly mail me the questions to mail id shobana.shanthi@gmail.com

1869


What is the restart inhabit setting in ABB spam150c relay (Motor protection relay)

3043


how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?

1399


can any one provide me a connection wiring diagram for a DG set control panel along with BOM?

1751


All the socket in a room become very hot, the Wall was also became very hot and the earth conductor also became live, what in your view might be the possible causes?

1205


What are the commonly used schemes for the bus zone protection?

545


hi frenz,its aswathy.i hve aplied for the hpcl test on feb,pls send the test patern & the placement papers as soon as possible. mail-id :kjaswathy@gmail.com

1311


if 2 coil of 1000W connect in series and 200 v is applied across it . then what is the total power of coil when coil have only resistive load .

1529