15hp,380v,31amp,3-ph submersible motor run at 250v what is
The temperature rise of submersible motor
Answer Posted / shubha_ee
If motor is fed from Delta connected supply.....
P=15hp = 11.19kW
so P per phase = 11.19/3 = 3.73kW..
pf = 11190/(1.732*380*31) = 0.55(lag)
then Vp=VL = 380V..
and
Ip=IL/1.732 = 31/1.732 = 17.9Amp..
So, R per phase = (380)^2/P = (380)^2/3730 = 38.71 ohm..
so, Heat dissipation for 1sec due to I^2R loss,
H1 = (17.9)^2*38.71*1 = 12403.07 Joules...
Now, if the VL=250V = Vp then IL= 11190/(1.732*250*0.55) = 46.98Amp...
so, Ip=46.98/1.732 = 27.12Amp...
So, Heat dissipation due to I^2R loss for 1sec ,
H2 = (27.12)^2*38.71*1 = 28470.98 Joules...
Now, increase in heat dissipation = (H2 - H1) = 16067.91 Joules
so, increase in temperature is 8.46 deg Celcius.....(as 1degC = 1899.1005 Joules)
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Please clarify 1. Icw: rated short circuit working withstand capacity 2. Icu: Rated ultimate breaking capacity 3. Ics: Rated service short circut withstand capacity 4. other specification of ACB
What are the no-load losses for the 11000/415V transformer with the following rated capacity? 1.1500 kVA 2. 2000 kVA 3. 2500 kVA 4. 3000 kVA
full form of flry b
how to get electrical supervisour certificate in gujarat
How LT megger works ?
What will be the current drawn by HT motor, if low voltage is applied.. any formula to calculate the LT amps of HT motor.?
can mini-curcuit supply MIL-tested transformer !
What is effect of harmonic current (Draw by VFD) on power system/ electrical Equipments ?
What is method of calculating the fault current for a MDB, 50KW, 3PH, 415V, 50HZ?
In a power conditoining unit (inverter) of a solar plant when we measure the d.c. current fed by different strings of solar plates to inverter, the current in the negative wire is less almost by 1 ampere to the current in its positive wire say current in positive wire 5 A , then current in negative wire of the same string is 4 A. Since the current entering should be equal to current leaving then why the current is noticably less in negative wire.
we can run 2phase as 3phase .what will be the differnce with respect to phase angle, power, current between the two modes
Why are iron cores in transformers made laminated?
Is there any specialised book to refer about fault level calculation both in MV and LV side??
what is smart grid? why we use it? explain in detals bcoz i want give presentatin from it....
How many capacitors using in LT panel as per Govt rules?