how far the two wire transmission (loop power) maximum distance suitable?
Answer Posted / rampal.m.
Power supply is 24vdc this can be load wear upto 600 ohm minimum operating voltage 10.5vdc for load 250 ohm (abb tx) so minus the load 600-250 =450 ohm from graph.
Now inst cable copper conductor has resistance per km approx= 25 ohm/km then divided 450/25=18km.
Answer=18km .
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Q1: Consider part of a control loop, which excludes the transmitter, consisting of a process, a controller and a control valve which may be represented by two dead times of 0.5 min each and three exponential lags of 0.8 min., 1.0 min. and 1.5 min. respectively. We wish to express this system as an overall first order plus dead time (FOPLD) model ie gain, time constant and process dead time. (We will see later that this is often done, to simplify controller tuning). For this exercise, gain is considered to be 1.0. (A) If the transmitter is a flow transmitter whose behaviour can be described by a dead time of 0.2 min. and an exponential lag of 0.5 min. in terms of the overall dead time and overall first order lag how can the system behaviour be approximated ? Overall dead time = Overall time constant = (B) If the transmitter is a temperature transmitter with a temperature sensor in a protecting well whose behaviour can be described by a dead time of 0.7 min. and an exponential lag of 15 min. how can the overall system behaviour be approximated now? Overall dead time = Overall time constant =
What denotes the 5/8mm in the 3300XL 5/8mm proximitor probe?
How it the difference between force balance system and dispalacement balance system?
Yokogawa CENTUMVP R6.09 unable to download to Engineering Station with ExaOPC R3.75
The issue is when I try to download the common project section to the Engineering Station (STN) from the HIS in System View, it is unable to connect. The error displayed is:
WARNING: Could not connect to equalize destination. (7001)
Retrying. Number of retries = 0/1
ERROR: LdXopsLoadMain: connect error 10060
ERROR: Processing terminated due to connection error. (7002)
Equalization end with errors. STN0149
---- ERROR = 2 WARNING = 1 ----
Background:
>Updated the ExaOPC software on the STN from 3.60 to 3.75
>STN operating system is Windows Server 2008 R2
>HIS operating system is Windows Server 2016 Stanard
Solutions attempted include:
>Ensuring all IP addresses are correct and all networked devices can be pinged.
>The ability to ping a device using its host name from another device (
Type of level transmitter commnly used in Procees area are the following. a.________________This type of level transmitter works as follows
How to Calibrate Radar Level Transmitter in Field
steps for installing orifice plate?
How to Calibrate Flow Switch in field
Exothermic reaction./ endothermic reaction
SOME OF YOUR QUESTIONS ARE NOT MAKING ANY SENSE SO TRY AND PUT IN A LITTLE BIT MORE EFFORT BEFORE YOU POST A QUESTION. WE WILL ONLY HELP THOSE WHO WE CAN SEE ARE TRYING TO HELP THEMSELVES.
Why grounding is necessary? Give example with diagram.
How to calibrate Field bus transmitter? procedure ?
how to measure draft pressure in transmitter pl. give its single line digram
on interface level transmitter model(RTG3302-EMERSON) What is threshold valve how can we select correct threshold value T1,T2,T3,T4 When interface water & hydro carbon
Make Heater Process Logic.