why induction motor having low power factor at starting time
and high at full load.

Answer Posted / suman pakhrin

cos∅=R∕√((R2)²+(s.X)²)

During starting,reactance of rotor is maximum Xr=X since slip=1
as load increases slip decreases and so does the reactance
as Xr=S.X therefore its obvious from above that during starting the impedance offered by rotor is more inductive as that during loading conditions!and hence power factor at start low compared to loadin conditions

Is This Answer Correct ?    23 Yes 9 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Why it is possible to use PWM with a STATCOM and not with a conventional TCR based SVC

1573


At the starting of dc motor and syn.motor and induction motor high current flowing through the winding. Due to this the windings burnt out. To avoid this different types of starters are used. But incase of transformer what Will be used (At starting no emf is induced in the primary winding)?

1537


IN electrical field, WHAT ALL THINGS THE CUSTOMER WILL ASK WHILE ORDERING FOR LT PANEL (ALL TYPES OF LOW TENSION PANEL)

1628


where is the need for short circuit test for 3 see is required and why? can you explain in brief with application

1407


is it possible to turn on the single phase star delta on delay timer using 24 v dc ?

1467






what are the basic insulation levels & what its Unit

1491


Dear all, i completed M.E(Power Electronics & Drives) 2011 passed out having 78% so i need job in core side but i don't know how can i receive the calls from electrical companies and i uploaded my CV in naukri, times jobs etc.. In that iam not recieved any mails from good companies so give me best procedure plzzzzzzzzzzzzzzzzzzzzzzzz..... Thanks, K.Linga Reddy Email-id:-lingareddykmthm@gmail.com Ph no:-08015402078

1401


Please explain the following and how these are working with PLC unit 1.I/O Module 2.I/O Device 3.Adaptor Card 4.Ribbon Adaptor 5.RS 485-FC

1173


How will you justify IR value and Charging voltage of any motor,transformer and Cables.......???? . . . . . . . . Plz tell me any body Baljeet Singh, engineer_89@refiff.com

1617


what is protection class current transformer.

3428


As per standard, transformer body earthing and other Equipment earthing (Equipment earthing) did not connect. but in LT side termination we are doing metal glanding in both side Transformer to PCC Panel through armoured cable, now X'mer body earthing and PCC Pane earthing (Equipment earthing) both are connect.is this safe for X'mer or other equipment?

1193


what is the maximum permissible limit value of leakage current and leakage counter reading to replace lightining arrester?

4626


What is the function of a neutral reactor.

1310


Sir, My doubt on cable sizing calculation, Load:74 KW calculated cable 1 run 50mm2. Now client asking us to reduce cable size by increasing runs. Sir, My question now when my mind strikes with 2 options 1) Divide load 74/2 = 36 and calculate cable for 36+36 making it 2 runs or 2) Simply i can divide 50mm2 /2 ie. 2 runs of 25mm2 Please suggest me sir

1426


what is the transformer turn ratio formula and give some examples?

1922