Answer Posted / rijo dennis
A Flow transmitter will produce 4-20mA as its output. According to the differential pressure applied to the diaphragm of the D.P it will produce electrical signal. In the cause of the flow the out put current will be in the square root proportional mode, i.e
input= 0% then output= 0% 4.00 mA
input= 25% then output= 50% 12.00 mA
input= 50% then output= 70.71% 15.31 mA
input= 75% then output= 86.60% 17.85 mA
input=100% then output= 100% 20.00 mA
For a level transmitter it will be operated in linear mode,i.e,
input= 0% then output= 0% 4 mA
input= 25% then output= 25% 8 mA
input= 50% then output= 50% 12 mA
input= 75% then output= 75% 16 mA
input=100% then output= 100% 20 mA
The same DP(Differential pressure) Transmitter can also used for both flow and level,but the one and only change in the mode of operation. flow is proportional to the
square root of the DP,but floe is directly proportional.
| Is This Answer Correct ? | 10 Yes | 0 No |
Post New Answer View All Answers
what is interface level and how it is calibrate?
What is the difference bitween control net scaner and device net scaner
installation process of orifice,a question asked for confusion creation in interview by BARC 1.if orifice is tightly fitted with pipe ,it will act like venturi 2.if orifice is left hanging in between liquid it will not create the pressure difference exactly,
Basically iam Instruemntation Engineer, but Iam interested in Instruments design engineering, so plz guide, is there any course, training or Softwres to become Instrument design engineer??.
hello can yoy pls send me previous papers of jindalpower and steel ltd.....'m from instrumentation..... mani1048@gmail.com
Explain bernoulli’s theorem. State its application.
is motorized valve closed when power shutoff?
can you send remote seal interface level transmitter calculation steps for oil water saperator.
Hi i m B.E. In elect. & comm. I m workin in bio mass plant from 6 mnths as inst. Engg. but now i m in dept. Of operation as shift engg...which is best operation or inst. 4 me? M confusd..plz help and reply me..
I want measure the volumetric flow of gas in waste heat recovery Boiler?Tell me how and which type of instruments required. Plz mail me:naba02222@gmail.com Sam please post the answer .
I am having a Phoenix digital to modbus converter. The o/p of the same is connected to flow computer FB407. But the digital signals are updated only after one minute in the flow computer. what may be the cause of delay in communication? Flow computer is having a scanning period of less than 1 sec.
Identification of ss fittings, pilot valves, relief valve.
Why is it necessary to use compensation leg to measure the liquid level in a closed or pressurized tank?
Define cryogenic?
Explain signal isolator