How to calculate incoming cable size for 33KV, 1MVA transformer.
Answer Posted / ak
calculate line current for transformer
I=1000000/(1.732 x 33000)
=17.50 Amps
based on the value of current select appropriate cross section area of particular gauge.
Is This Answer Correct ? | 6 Yes | 1 No |
Post New Answer View All Answers
Write the analogous electrical elements in force current analogy for the elements of mechanical translational system.
Difference between RCCB, RCBO and ELMCB.
WHAT IS THE TOTAL POWER GENERATION IN CHHATTISGARH?
sir i want previous entrance exam papers for written test
We need to current density & short circuit calculation at 65kA for aluminium & copper busbar.
What is your acheivements
what type questions asked in hp cl
What is main cause of cable's terminal point burned in Lug on high temperature although lug and cable selection is ok as per stantard and also tightness is ok as per situation. so please take in deep and tell correct answer thanku.
I want to put this query to SENIOR & EXPERIENCED ELECTRICAL ENGINEERS. 1)I want to know about the control circuit diagrams for control panels. I found it difficult to understand. Is there ant booklet through which we can learn the circuit diagrams? 2)I want to learn about conduiting, laying cables, preparing cable schedules and various techniques which is the part of building infrastucture(construction field). I don't have any experience in this area. I have experience in control panels only. that's why i am not getting any opening in building infrastucture (construction field).Can I get the job in this field as Trainee Engineer? How to enter this field? I need job in PUNE
What is the function of Governor in Hydro Power Station? What is the Function of Lightning Arrestor Voltage Transformer (LAVT)?
dg started in plc mode and load taken later one battery terminal connection will be disconnected by loose connection what will happen for dg and shall we connect battery terminals while dg in load time?
I am having a 42KW 3 phase electrical heating furnace, heating element is 80/20 nichrome material, my connections is made in such a way that 2 star connection compromising 2 coils per phase so totally 12 coils, shall if i use it unbalanced star condition (instead of 2 group of 3 phase or 1 group of 3 phase, connecting 4 phases of 5 phases) what will be the consequences and is it acceptable?
What types of CMOS memories have you designed? What were their size? Speed? Configuration Process technology?
what are the safety measures of induction motor?
What is proportional controller?