In dcs contol valve parameters showing like this
Gain=1 or 2 , ti=7 sec, td=20sec. But temp,pressure,level control valves we are using in which type parameter side using ti,td clearly tell me
Answer Posted / carl_ellis
Gain, ti and td are PID proportional control tuning terms/constants. PID controllers use PID tuning constants to calculate an output based on the error signal; final control elements (valves) do not do a PID calculation so valves are not involved with gain, ti and td. The controller is typically in the control room, the valve is somewhere out in the process.
A PID controller calculates the expected valve/damper position from the error signal and the tuning constants, the result of which is an output control signal ranging from 0-100%.
A valve positioner or valve I/P receives that control signal from a controller (4-20mA, Profibus) and supplies air or electric power to the actuator to achieve the correct position demanded by the control signal.
Ti is the term for reset or integration. It is used when the process itself is not an integrating process. Level, pressure, and pH are usually integrating processes. Sometimes temperature is an integrating process, sometimes not. When the process is non-self regulating/integrating process, the ti term is not used in the PID calculation.
Flow and temperature processes typically use the ti term for PID calculation.
An exception to the rule of PID being done in a separate controller is Foundation Fieldbus (FF), which allows function block PID execution in FF devices. In a case where PID control is executed in an FF valve positioner, then a valve would use the PID tuning constants.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
what do u mean by compensation n pid tunning?in pid tunning what you tunned?is it possible 2 tune p i d
what is difference between fork type and capacitance type level switch. where it is using
hello friends, can you please send me the model paper or question paper to be prepared for hpcl examinations????????? You can mail me at rahim_here@yahoo.com waiting for your reply........... help me .. plz.....
We are using Rosemount 5400 series Radar Level Transmitters in all types of Sump Applications having oily water hdrocarbon petrochemical nature. What we are facing the problem frequently is that always getting reading frezzed at some value. If we do power recycling , sometimes it is working . then making same freezing problem. If anybody faced before such type of problem and also having solution , Please give the answer.
Why we are using reverse action in displacer types level transmitters on some Vessels?
What is profibus?
How process line mpm calculation is done?
hello sir/madam, I,Subramanian need 5yrs placement papers of officer trainee of Instrumentation technology.pls send to this mail id mani_nxtgen@yahoo.co.in please do the needful. with regards, subramanian.v
i need some objective type questions in instrumentation
how u calibrate pneumatic n motorized c/v?
how to calibrate corollaries (Mass flow meter)?
What is difference of fanuc alpha series 16i and 18i controller.also what is differnce betn TC and MC controller
defination of radial vibration?
What is the GK Value in Flowmeter?
plz you help about Que paper of mahagenco previous your,any model paper relad to it{maharastra power genration}