Answer Posted / e mohana priya
A basic liquid sizing eqtn.. is as follows:
Q = C
V
∆P / G
(1)
where:
Q
=
Capacity in gallons per minute
C
v
=
Valve sizing coefficient determined experimentally for
each style and size of valve, using water at standard
conditions as the test fluid
∆
P
=
Pressure differential in psi
G
=
Specific gravity of fluid (water at 60°F = 1.0000)
Thus, C
v
is numerically equal to the number of U.S. gallons of water at 60°F that will flow through the valve in one minute when
the pressure differential across the valve is one pound per square
inch. C
v
varies with both size and style of valve, but provides an
index for comparing liquid capacities of different valves under a
standard set of conditions.
To calculate the expected C
v
for a valve controlling water or other
liquids that behave like water, the basic liquid sizing equation
above can be re-written as follows
C
V
= Q
G
∆P
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is the differerence between hysterisis and linearity.
How the sizing of the analog signal cable is calculate?
How to calibrate the flow transmitter
i have steam drum height 1000mm. and i want to placed the transmitter below the tap.how i calculate.
OBJECTIVE TYPE QUESTIONS OF ANALYTICAL INSTRUMENTATION
How can measure flow in oil line?which type of transmitter is generally used?
What is critcal speed. what is resonant frequency. why we want to cross crtcal speed on higher RPM (early).
how to calibrate corollaries (Mass flow meter)?
Sir, I want junior executive, Instrumentation question papaer for IOCL, Plz send to arabinda.ghosh83@gmail.com
what is Best Among SINK Or SOURCE Type Design In Digital Signal, Either Iput Or Output? WHY?Can any one..
what is output of FOUNDATION FIELD BUS transmitter
What is the difference between mmwc and mmwg?
basic connection and principle of axial shift sensor n differential sensors in tubine describes n draw......
what is interlock system and why we use of this?
what are the values of fuel flow rate in various places in boiler.