Why we use less dia. fuse and conductors at H.T. side, although we use higher dia. cables on L.t. side?
Answer Posted / al amaan
The size of the cable(Conductor) is choosed depends on the current value
For Example In 1000 KVA,11 KV/433 V Step down Transformer
Formula for calculate Power in KVA; P=√3*V*I
Current Formula; I=P/(V*√3)
Current in H.T side; ; I=1000/(11*√3)
I= 5.25 A
Current in L.T side; I=1000/(433*√3)
I= 133 A
From that the current in L.T side is higher than the H.T side So we use Higher dia cables in L.T side
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
I don't understand why when we connect high voltage source in DC to electronic motor , we must add capacitor and resistor in parallel ? (I know that we use capacitor because we want to absorb the current that in the first second electronic motor in opposed with current course produce. ) what are the feature of Resistor and in such situation ?
How to synchronization will be done between two DGs ?
If Dg set load increase 25%, How much increase fuel Consumption (15 kva 2 cylinder DG set)
How many kinds of E.L.C.B and how to work E.L.C.B
What are root loci?
a 230v transformer with step down ratio 19:1.it has 2000turns on primary and rated 25va calculate max primary current no of secondary turns volts/turn
Hello Friends, How can we recognize the CT Star Point is S1 or S2 in case of Electro Mechanical Relays and what is meant by Restraining coil in relays and what is the purpose of that.. thank you in advance..
I am completed DEEE in tamilnadu, now i am working in andhrapradesh with 2.5 year experience in relavent field. capacity of the tranformer is 11KV, 1MVA Transformer, i am eligible for getting c licence in andhrapradesh pl help me.
How RTCC panel is working and give single line diagram for RTCC with transformer?
i want bhel placement paper for electrical if anybody having pl send to my id kavitha867@myway.com immediately
Define unilateral circuit?
What is Delta Connection? What is meant by Forward Delta & Reverse Delta & How Will be the Connection in Power Transformers?
If 24 KVA AVR having Input voltage 200-400v, Output voltage 415+-1%, what will be the voltage if Load is 13A.
why power factor is important?
for hipot test on 33kV busbar, we will test on 70 kV or 56kV, what is the acceptable leackage current?