Can anybody please tell me which value(saturated or unsaturated) of sub-transient reactance(Xd") we take for the calculation of fault current of the system?

Answer Posted / sarmadahmed

Fault current calculations are usually done to find the rating of protection equipment. For this we need the maximum fault current. Since unsaturated machines has lower value of sub-transient reactance, we should use unsaturated sub transient reactance for the calculations.

Is This Answer Correct ?    2 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

in power generator normaly voltagr betwween esth to neutral is 0 but my work place generator show the volatge is 60v any body know why? thanks

1411


What is the effect on power factor, shown by a trivector meter; incase of reverse phase sequence. If the power factor of a system is lag what meter will show in case of reverse phase sequence connected to the meter. and What in case of lead.

1804


hi this is hema can anyone mail me previous years questions for the APPSC-A.E.E (in electrical stream.) ......thank u.

1455


how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING) I O (current operating)?

1735


where is core-type and shell-type construction suitable for transformers ?

1643






how a.c. genarator control power factor when its conected to grid supply by incrising or decresing excitation voltage.

2703


How is the speed of a DC shunt motor related to the armature current?

670


how to minimize earth resistance upto 2Ω, if the resistance is 6 Ω ?

1444


What is the abbreviation of NGT panel

1505


why induction motors are rated at 0.8 power factor.

1524


why single CT used in DOL starter power circuit?

2055


i need the curve duty cycle and amper for (150 kva @50% dyty cycle) transformer turn ratio :19 and vin 400

1621


What are the disadvantages of autotransformer?

648


H.t motor 6600 volt to same motor lt supply 440volt supply applyed to h.t motor to effect....

1464


Help need in transformer !? Hello Friends The parameters of 2300/230 v 50hz t/f is R1=0.286 ohm R`2=0.319 ohm Rc=240 ohm X1=0.73 ohm X`2=0.73 ohm Xm=49.2 ohm Secondary Load impedance ZL=0.387+J0.29 solve the exact equivalent circuit with normal voltage across primery.. I know every thing but i cant find CURRENT I1=? and I`2=? Please help me give solution or only Formula please please...

2503