how to calculate flow range in DP tx
Answer Posted / carl_ellis
how to calculate flow range in DP tx
A flow range is calculated for a primary flow element
according to design flow conditions. The result of the
calculation is a maximum flow rate at a given DP span.
The DP transmitter does not 'calculate flow'. The DP
transmitter is spanned to the value in the calculation.
The DP transmitter can extract the square root from the
normalized percentage of the DP. That square root value
can be assigned flow rate values in fieldbus transmitters.
Or the square root value can be assigned flow rate values by
the local indicator on the DP transmitter. But the square
root 4-20mA output is just a signal representing the span of
the flow rate. Flow rate values are assigned by scaling in
the receiver.
Carl Ellis
Measure First
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
describe flow nozzel principle?
PLEASE PROVIDE SAMPLES OF CHEVRON SKILL TESTS
Working principle of magnetic flow meter ......and calibration procedure of e+h magnetic flowmeter...
How to calibrate Toxic gas detector?
Calibration of controller (pneumatic)
Sir, I am working as a Instrument Engineer in Grasim Industries. Can any body provide question answer for interview purpose
Describe a time when you anticipated potential problems and developed preventive measures.
how to calculate control valve bonnet size?? or how to select its material?
what is interface level measurement.who can calibrate interface level measurement transmitter online
What is the basic difference between Modbus and CAN Open Protocols
plz send me general of ongc
detail of mass flow meter pricipal
What is Alpha & Beta fctors related to Orifice Plate & its relation with flow?
A valve in series with an orifice plate (DP transmitter), is aligned for constant pressure in the pipeline, if there is an error dx, How to align it in process.
why is an oxygen sensor used in a boiler stack