Our Company's Contract Demand is 110 kVA. We use 12
Capacitors each of 12.5 kVAr Capacity to maintain Power
Factor of 0.99. So, what steps should we take so that our
Contract demand does not exceed 110 kVA?

Answer Posted / 7anoter4

In order to know how much capacity to use one has to know
what is the now the actual power factor. Let’s say the
actual power factor is 0.8.Then the reactive power is
110*sqrt(1-0.8^2)=66 kVAr.
If the power factor is 0.99 then the reactive power from
the Utility will be 110*sqrt(1-0.99^2)=15.5 kVAr.
You have to compensate the difference 66-15.5=50.5 kVAr so
4*12.5=50 kVAr it is enough.

Is This Answer Correct ?    7 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

in a silicon diode we can measure .7v in a voltmeter.but why we can't use this voltage for using?

1447


what are the safety measures of induction motor?

1565


what is breathing?

1319


What is the difference between rulling span and wind span of of an Over Head Transmission Line?

1818


What Is Sampling?

764






10 Mtr Hight of Lighting Arrestar how much area coverd??

2007


The power supplied to a 33microF capacitor from a 120V, 60Hz source will be

1618


Explain the advantages and disadvantages of hydropower plant?

654


slipring induction motor starting time Lrs operating why lrs starting time lrs outer body didn't get shock

1456


Is a d.c.compound motor is use as a booster? how?

1636


the problem faced on star or delta winding connection??

1476


I want to know the 'Test voltage' for Tandelta testing of 3.3 / 6.6 / 11 KV Motors. Please explain

1776


what are the differant std sizes of cable trenches?

1520


If one lamp connects between two phases it will glow or not?

603


is it true there's a big difference in using Cummins or Denyo...especially power output or leakage

1381