Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Our Company's Contract Demand is 110 kVA. We use 12
Capacitors each of 12.5 kVAr Capacity to maintain Power
Factor of 0.99. So, what steps should we take so that our
Contract demand does not exceed 110 kVA?

Answer Posted / 7anoter4

In order to know how much capacity to use one has to know
what is the now the actual power factor. Let’s say the
actual power factor is 0.8.Then the reactive power is
110*sqrt(1-0.8^2)=66 kVAr.
If the power factor is 0.99 then the reactive power from
the Utility will be 110*sqrt(1-0.99^2)=15.5 kVAr.
You have to compensate the difference 66-15.5=50.5 kVAr so
4*12.5=50 kVAr it is enough.

Is This Answer Correct ?    7 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

raleigh method

2136


Why we used 690V in ACS 800 drives.Why dont use standard voltage like 415v or 1.1Kv

2500


what is the differance between HT motors And LT MOTORS.

2036


We have two APFC panels in same station. I need how to connect CT in two APFC panels.can we take one CT in series connection or two separate CTs.

1573


HOW DOES THE ELECTRONIC ENERGY METER WORKS?

2213


when we have to purchase the transformer by own i.e how much load will preferred HT connection?

1720


what is interfacing in computer studies?

1823


What is meant by bus bar protection?

1257


Why there are some equipment(i.e:TV) that using 2-pin plug instead of three? What happen if there is current leakage? Are we going to get electric shock??

2245


Why HT 11 KV Slipring Motors are connected in star ?

2275


how we calculate torque ? how we improve it ?where torque will either motor or generator ?

2111


Why i receive the GCU fault in my DG Sychronization panel . what all the factors considered for this fault .

2275


why in a swquence network representation, the negetive sequence generated voltage is taken as zero?

2064


Explain and give me an example of a time when you had to explain some new procedures to your co-workers for quality service delivery, how did you go about it?

2032


How to control motor gearbox speed and friquency? If length of cable and dia given, how to measure the voltage drop?

2081