HELLO FRENDS ,, I M IN THE MIDST OF TROUBLE .. JUST LITTLE HELP ME...
SUPPOSE ,, I HAVE A CLOSE VESSELE TANK ( HEXANE MEDIA ) ,,
I M USING ROSEMOUNT 2051 DPT FOR LEVEL APPLICATION ..
ITS CALIBRATE RANGE IS.. . 0 TO 950 MMH20 ..I DID CALIBRATED DPT WITHOUT
REMOVING IMPULSE LINE OF HIGH AND LOW TAPPING.. & WITHOUT DISTURB 3 WAY
MANIFOLD..!!!
BUT ,,, DURING CALIBRATION I SELECT RANGE BY HART LRV IS 900 MMH20 & URV
IS 1300 MMH20 ,, BUT ,TANK LEVEL SOMETIMES 100 % AT 1100 MMH20 ,
SOMETIMES 1300 MMH20 ..IN THIS CONDITION .. WHOLE LOOP FAILED ,, MAIN
THING IS THAT ,, HOW TO CUSTOME RANGE SELECT ?? AND IF I USED RANGE OVER
THE ORIGINAL CALIBRATE RANGE ,,,THEN WHAT ERROR WILL BE COME ??? HOW TO
ZERO CALIBRATION OF DPT... HOW TO ZERO TRIM BY MANIFOLD ?? AND FOR TANK
LEVEL PURPOSE ... WHICH UNIT I CAN USE ??? IS THERE ANY CALCULATION OR
CALIBRATION .. IF YEH .. THEN PLZ JUST GIVE ME CALIBRATION STEPS FOR DPT..
THANKS YOURSSSSSSS
Answer Posted / carl_ellis
There is insufficient information to determine what the
correct range of the transmitter should be.
1) Is there a capillary with remote seal on either side of
the DP xmtr? If so describe in detail.
2) Is the DP xmtr mounted directly on the lower flange? If
not how high above and below the lower flange (tap) is it
mounted?
3) Is the DP xmtr high side connected to the lower flange (tap)?
4) Is the low side a dry leg or wet leg?
5) What is the specific gravity of the material in the tank?
6) If the low side is a wet leg, what is the specific
gravity of the fill fluid in the wet leg?
7) What is the elevation distance from the lower flange and
the maximum level?
8) what engineering units are used for level ? mm H2O?
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is super thermocoupal?
I want to know the questions asked in ONGC interview(after being selected in the written exam) for Instrumentation branch.Kindly help.
can anyone tell me about the basic concepts to consider before to start a PLC panel wiring
1. For Steam drum level signal, why do we compensate with drum pressure signal? 2.For main steam Flow signal is comensated with main steam temperature signal and main steam pressure signal why?
how to calibrate steam control valve in steam turbine
I faced several time siemens ps2 positioner automatically getting Chang in it's set point direction after auto calibration So is there any causes biside this or any permissives ?
send me HPCL paper
Full form of KKS when use DCS.
I have a Control VAlve having size of 2 ".Only the known parameter is Pressure drop . Its 2 Kg. Then How to calculate control valve sizing means Cv.
what is maxdna ?. explain about the software details.
Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.
what deference between panel earth and systemearth
how many types of preheaters are in cement industry & what r they can any body explain?
Instrument QA/Qc what is the project quality plan?conduit inspection RFI. which documents attache with package?
how to convert cubic metre per hour to newton cubic metre per hour