what is the CT of protection and CT of metering ? what is
class 5P10 & 5P20 and class PS ?

Answer Posted / er.k.k.murty

From: Er.K.K.Murty, B.E.(Hons)Electrical,FIE.
Retd.Chief Engineer(Testing & Commnu),M.P.State Electricity
Board.
Jabalpur(INDIA).
Email ID:kkmurty05@yahoo.com

Measuring Current transformer: This is also known as
Metering CT ,it should confirm to IS:27O5-2 or IEC-60044-1
The cross section area of the cores are so designed that
,the core saturates at about 5 times the rated current (with
low saturation current) .This would facilitate safety to the
instruments, while heavy fault current flows in the Primary
circuit.
Before going into the details of characteristic / duty to
be performed by the metering CTs, one should be aware of
some definitions / terminology relevant to the equipment.
7.1 Instrument Security Factor (IFS/FS): The ratio of
instrument limit primary Current to the rated primary current.
Note: In the event of system fault current flowing through
the primary winding of a CT, the safety of the apparatus
supplied by the CT is greatest when the value of the
instrument security factor (SF) is small.
. Rated Instrument Limit Primary Current (IPL): The Value
of the minimum primary current at which the composite error
of the measuring CT is equal to or greater than 10%,while
the secondary burden is equal to the rated burden.
Note: The composite error should be greater than 10%, in
order to protect the apparatus supplied by the CT against
the high current produced in the event of system fault.
8.0 Accuracy classes;

(a)Standard Accuracy classes: 0.1,0.2,0.5 and1.0 class-The
accuracy limits are defined from 5% of current onwards,
however the declared accuracy limits ie 0.1,0.2,0.5 & 1.0%
respectively and 5,10,30,60 minutes respectively would be at
100% to 120% of rated current at 25% to 100% of rated
burden. {Ref:IS:2705(part-2)}
(b)Special Application Accuracy classes: 0.2S and 0.5S are
used for special applications. The accuracy limits are
defined from1% of rated current, however the declared
accuracy limits ie 0.2% & 0.5%and 10&30 minutes respectively
would be at 20% to 120% rated current at 25% to 100% of
rated burden. Precision metering of High value HT consumers
and Tariff meters etc are categorized as special application
metering and need ‘S’ class CTs. {Ref:IS:2705(part-2)or
IEC:60044-1}.
Note: Almost all the Distribution Utilities follow the
convention mentioned here under;
(i) 0.2 and 0.2S are used for the voltage above 33kV level.
(ii) 0.5 and 0.5S are used up to 33kV level.

5P10 & 5P20 Class CTs: They are generally used for Over
current (Instantaneous and IDMT relays) and E/F protection
of Feeders, Transformers etc.
5 signifies the % limit of composite error
P signifies Protection core,
10, 20 signify the quantum of fault current as multiples of
the rated current or ALF(Accuracy Limit Factor) up to which
the CT shall have the defined percentage of composite error
i.e. ± 5%.
Standard Accuracy Limit factors as per IS: 2705 and
IEC:60044-1 are 5, 10, 15, 20 & 30.
Accuracy limit factor is inversely proportional to the rated
burden i.e. if the burden is lower than the rated one, the
limit of accuracy shall be maintained beyond the declared one.
The formulae for actual ALF;
ALFACT= ALFRTD x (Sin+Sn(Rated Burden))/( Sin+Sa(Actual
Burden)).
Example:- Calculate actual Accuracy limit factor if
secondary burden is reduced to 1/3rd, if CT rated as 200/5
A,5P10,15VA and Rct =0.15Ω?
ALF Rated=10(From CT data 5P10),
Sin (Burden due to internal resistance of the CT) = (5A)2 x
0.15=25 x 0.15=3.75VA,
Sn (Rated burden) = 15VA (From CT data),
Sa(Actual Burden) = 15÷3= 5VA,

ALFACT = ALFRTD x (Sin+Sn(Rated Burden))/( Sin+Sa(Actual
Burden))

ALFACT = 10x ((3.75+15))/((3.75+5)) = 10x18.75/8.75 = 21.42
It is clear from the above example that the ALF increases if
the connected actual burden is lower than the rated one. The
CT in this condition shall maintain accuracy up to fault
current of 21.42 times of rated current as against 10 times
the rated current and shall not saturate till then.
PS Class CTs: Though abbreviation PS is not elaborated
anywhere, however it may be called as “Protection Special
Class” CT core. This core is used particularly where current
balance is precisely required to be maintained. In
Differential protection, balance is the prime requirement
between secondary currents of associated CTs of either side
of the equipments. Differential and restricted E/F
Protection of Transformers and Overall Differential
Protection of Generators need such CTS.
The 5P10P or 5P20 class CTs cannot match the Characteristic
as that of PS class. The core of PS class is such that very
high current is needed for saturation of the core. Knee
point voltage of the CT is of valid importance. The
developed voltage across the relay terminals should be lower
than the Knee point Voltage of the CTs.

Is This Answer Correct ?    48 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

In India the supply voltage is 230 volt A.C. During the negative half cycle phase becomes neutral and neutral become phase? or what will happen during negative half cycle? how the electrons flow during positive and negative half cycle?

1492


How isolater function when installed inelectrical 440V wiring

1704


why is control bus bi-directional?

1705


what is die electric strnth of transformer ?

1647


How to calculate fault level of 11 KV system

1512






why T/F winding temp measurement cts are odd secondary current ie,109A/1.2A/1.4A?

1376


hello everybody. what does an abnormal stator winding impedance or dc resistance show? thanx

1479


What is the use of Surge Capacitor in LAVT?

12901


some time we open engine breaker 8.0 MW load but plant not trip. and another time engine open 4.0 MW load engine trip why? individually engine breaker open & individually emergency stop why difference?

1309


in dc suppy frequency is zero why? if dc frequency is zero how to exist dc transients and ac transients

1555


What is evaporator & condencer & compressor

1732


How to convert a two phase power into a three phase power in induction machine?

1352


what is feeder bay?

1112


what is differnce btwen lll and lllg faults

1512


What is mason's gain formula?

778