I am new guy as an electrical engr. in a 100MW HFO based
power project. I am in operations division. I have noticed
from last few days, my supervisor sends the last 24 hours
energy generation calculation to my plant manager. I have
noticed, he calculated last 24 hour's generated energy
differences in KWH then he multiplied it with a multiplying
factor 960. for example:
total difference =2.685 KWH*960= 2577.6 MWH.
but he does not not know what is multiplying factor 960??
can anybody explain it??
Answer Posted / sonu pal
First of all you will find CT & PT ratio using for this
power measurement then you can find MF what your supervisor
apply.
Suppose that---
you are using a 33 kV CT having ratio 50/1 Amp. and 33 kV
PT. so multiplying factor= 50/1 * 33000/110 = 15000 (in watt)
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
If an electrical component has a positive temperature coefficient, how come such components have high power losses due to heat if current decreases when resistance increases? assuming power given by I^2*R whereby the Resistance is infinite.
In Electrical 'Single Line Diagram' cable nomenclature shows "2 X 1C X 630sq.mm to be provided for one incomer. The question is how many cable to be proved for one Incomer.
Define conversion efficiency of a power amplifier.
how to decide the panel size like MDB ,SMDB PANEL SIZES
WHAT SHOULD BE THE BEST CURRENT RATINGS (PRIMARY / SECONDARY)FOR A CT INSTALLED AT THE INCOMING 11KV PANE? WILL IT BE CALCULATED ON THE BASES OF MAXIMUM DEMANT VALUE OR ON SUM OF ALL TRANSFORMER'S KVA? NOMALLY MAX DEMAND REPRESENT THE MAXIMUM OPERATING LOAD OF THE PLANT AND TOTAL KVA OF (SAY 5 NUMBERS TRANSFORMERS) REPRESENT THE CONNECTED LOAD. WHICH i.e. MAX DEMAND KVA OR CONNECTED KVA ARE BETTER TO USE FOR CT CURRENT CALCULATION? PLEASE ANSWER.
what kinds of Transformer oil grade is better for power transformer ?
how a resistor resists to flow the current?how an inductor oppses the sudden change in current?how a capacitor opposes a DC voltage.
can we use engine degreaser for electrical motors?
Why use the vcb at high transmission system ? Why can’t use acb?
Define pole pitch?
If i have two 3000 kW motors and the whole facility requires a 10 MVA transformer. What would be better installing two 5 MVA transformers(one for 1 motor ) or just a single 10 MVA transformer for both of them. Give reasons for your answer.
We normally make oil soak pits under Transformers. Oil from soak pit goes to collection pit. We provide granules/pebbles under transformers. My question is weather granules/ pebbles to be filled in soak pit or not? if yes upto what level?
1)how to reduce the value of tan delta of trasformer and CB,bushing,CT&PT,CVT ? 2)how to reduce the resistance of CB contact and its operating time? 3)plz.....send me the project report on conditioning and monitoring of substation equipment on my email id (gusaiyogendra03@gmail.com)
How we can calculate the life of Lead acid battery
Explain the propagation of harmonics in the network and influence of phase angle of harmonics.