Why we use 250 ohm resistor in series with HART protocol
communication?
Answer Posted / zaldy
the 250 ohm resistor converts the 4-20 mA analog signal from the HART transmitter to a 1-5 volt drop to allow the Analog Input card of the DCS or PLC to read the analog signal. The HART digital FSK (Frequency Shift Keying) signal is also present on this line and supplies the HART digital data to the HART modem chip usually present on the same Analog Input card for all new DCSs and PLCs. The Bell 202 protocol used for this FSK
digital circuit needs no terminating or load resistor. The 250 ohm resistor is only for the analog circuit.
| Is This Answer Correct ? | 0 Yes | 2 No |
Post New Answer View All Answers
can we replace a slot sensor (inductive type) with limit switch (potenial free contact / no-nc type).
What is Cavitation in a control valve?
Explain the difference between plc and cnc?
Whether the DI, DOs shields can be connected with Analog Input Shield Earthpit?
What is eddy current? Describe the operating principle of proximity probe.
What is the calibration procedure of Drum level transmitter if range is 0 to -400 mmh2o in lab?
How to Calibrate Level Troll in field
you must show the examples application and give at least 4 types of transducer/sensors that can minimize the failure during the manufacturing of the resistors.
installation process of orifice,a question asked for confusion creation in interview by BARC 1.if orifice is tightly fitted with pipe ,it will act like venturi 2.if orifice is left hanging in between liquid it will not create the pressure difference exactly,
what is your eligibility criteria for freashers?
Which products are available in the Mass Systemswitch and System Manager AC range?
Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.
How we can check the 2 wire proxy switch? & how it is connected to DI MODULE OF PLC?
what is the calibration procedure for magnetic flow meter @ onsite
How to fix back the valve actuator stem