in short circuit. test of a
transformer 5 to 10%
ofvrated voltage is used why??? if
we use rated
voltafe then what will be?
Answer Posted / 7anoter4
The 5-10% of rated voltage represents the short-circuit
voltage that means if you connect all the secondary
terminals of the transformer together-it is a “short-
circuit”. If you supply the primary winding terminals this
short-circuit voltage you’ll get the rated current-primary
and secondary.
If the supply voltage is the rated voltage you’ll get the
short-circuit current [10-20 times the rated].
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Can we use shunt trip coil instead of trip coil with protection relay for protection?
What is the difference b/w fanuc alpha series 16i and 18i controller. what is stand for i
How to select the proper VSD to operate high inertial load
why the pf of semiconductor device is improved the electrical devices
How can i get my certificate of competency as an electrical supervisor? I have complicated my B.Tech from Uttarakhand technical university this year (2012).
what are the analog quality input for protection function?what are minimum reqiments?
how to calculate the no load current in transformer?
WHAT IS ELECTRICAL MAINTAINTENCE ?
What is the rating of a circuit breaker needed for 300 kv load in 33KV supply line of 33/415 transformer ? Whether 800/1200 amp vaccum circuit breaker can perform for a 33 KV line in input in 415 volt in output of the transformer ?
how to i get B licence,i am completed BE electircal and electronics engineering.i want to konw the proceduure to get b licence
CALCULATE THE TOTAL VOLTAGE DROP AND SELECT THE CABLE SIZE IN MM-SQARE FOR A PANEL-262KW AT 110 METER FROM THE SOURCE SUPPLY , SUPPLY VOLTAGE 240/415
What is an order of a system.
What are the types of windings according to the construction?
what is the difference between electrical and electronic choke?
Sir,In our company there are 3 caterpillar make(capacity:(1) 3.3KV,2.5MW(2)3.3KV,2.5MW & (3)3.3KV,1.9MW) & 1 deutz make (capacity:11KV,3.8MW)gas engines utilised,all are running in paralell. There are three transformer utilised,(1) 6.25MVA,3.3KV/22KV,Impedence voltage:6.7% used for two generator,both are 2.5MW(2)5.5MVA,3.3KV/22KV,Impedence voltage:7.2% used for one generator of 2.5MW & (3) 5.5MVA,11KV/22KV,Impedence voltage:7.8% used for one generator of 2.5MW.all generator breakers capacity of 1250Amps. Sir,I want the details of fault level calculation of generator,transformer individually & for whole system. If you require any information from me.feel free for contact me sir.pl.send the answer of my question as the earliest as possible.