how to claculate the ups load in KVA pls give the if any
fourmoul?
Answer Posted / nagarjuna
Consider
Emergency Lighting Load = 11.75 KW
Power factor = 0.80
Total UPS load for emergency lighting= 14.69 KVA
Installed capacity with 20% extra = 17.63 KVA
Hence 1no of 20 KVA is selected
| Is This Answer Correct ? | 0 Yes | 0 No |