Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

wht is Zero Elevation and Zero Suppression?

Answer Posted / kranti

zero suppression: when a dp type level transmitter is
installed below the hp tapping then we have to measure the
distance between the hp tapping and the transmitter and we
have to consider this distance as zero of the transmitter
while we are doing the calibration. and also add to the
actual span also.

zero elevation: if the transmitter is installed above the hp
tapping, we have to take this distance between the tapping
and the transmitter and we have to subtract from the actual
zero and also from the actual span while doing the calibration.

Is This Answer Correct ?    17 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

dear sir we have insatlled positioner model no.sipart PS2 make Siemens at our control valves . now problem is if we want to increase the response of valve opening speedy /fast. what parameters do we change for positioner ? any idea. please guide us.

1946


What is the advantage of using locally fabricated hook ups over Pre fabricated hook ups in process instrumentation?

2092


what is surge and how is it prevented, what is the purpose of bypass valve across AS valve.

2031


in valve is constructed as per SME B 16.34, then which standard is used for fire testing of valve?.

2063


Reason for capillary type dp level transmitter fluctuation

2026


while am calibrating Drager polytron 2IR flame gas detector occured non zero status.how can i get zero status?

2246


Why even multiple power supplu r used in instrumentation system?

5066


Why plc require in analog input 4-20amp & 0-10 volt?

1195


Can I calibrate the Electromagnetic Flow Meter on line and How.

2011


how to calibrate corollaries (Mass flow meter)?

2229


hello can yoy pls send me previous papers of jindalpower and steel ltd.....'m from instrumentation..... mani1048@gmail.com

2041


which type of zones used for boiler? & why ?

1910


How is work 5/2 sov?

1944


what are the different types of Protocols? & their applications.

30903


what are procedure of sox-nox calibration

3034