What are the most frequent problem faces with Vortex flow
meter?
Answer Posted / carl_ellis
Installation error - there is insufficient upstream and
downstream straight run piping for flow conditioning.
Failure to understand that all vortex do low flow cutoff at
approximately 10% of flow because there are not enough
vortices formed to produce an accurate flow rate
measurement. Low velocity flow rate in a steam header can
indicate zero flow even when the boiler is operating with
reasonable loads.
Corrosive fluid destroys the thin sensor membranes.
Carl Ellis
Measure First
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
How vortex sensor used for steam flow measurment can be checked on line i.e without taking out from process line.
Why 4-20 amps is being used in instruments? Why cant we use any other range instead of 4-20 amps? Why only 4 amps is taken as lower limit and why 20 amps is taken as the higher limit?
hello sir/madam, I,Subramanian need 5yrs placement papers of officer trainee of Instrumentation technology.pls send to this mail id mani_nxtgen@yahoo.co.in please do the needful. with regards, subramanian.v
How many types of sensor
Which type of diagphram use in costic line,DM water line,natural gas line,oil line?
What are the error values can accepted in flow transmitter calibration?could u give any formula for this?
Tell about your IFFCO plant visit.
Please can anybody help for control valve sizing step by step procedure?
How we calculate orifice plat size???
Why are the uses 24vdc in industries
Specific gravity.
How many interlocks at turbine side?
Why plc require in analog input 4-20amp & 0-10 volt?
What is the calibration procedure of Drum level transmitter if range is 0 to -400 mmh2o in lab?
Coal mill Instruments Equipments for cement plant And process diagram ?