we use Dyn11 trafo for distribution purpose, if it`s possible
for replacing Dyn1. if it`s change means what will happen?
Answer Posted / 7anoter4
If this transformer works in parallel with other
transformer of the same connection type it is not possible
–the angle between supplied voltage will be 300 degrees [or
60 degrees] and will provoke a short-circuit equal to
Vstator/2/Ztrf .
If the transformer works alone it will be ok [no any
difference]
Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
checking procedure of capacitor based motors.used in fans etc?
Why dry type cast resin transformers tap link blast in HV side while power shut down times on load?
working principle of oil startar
State any two nuclear power stations in India, with their generating capacity.
what will happen if OLR CT in all phases are short circuted
i applied for the ap transco please forward the freqventley asked QA
Hi My dear all Friends, There is a question regarding HVAC Engineering and widely used in Power Projects. Question- What is the diffrence Between REF, SEF and Differential Protection....???? Where REF - Restricted Earth Fault SEF - Senstive Earth Fault.
What is marx circuit?
What is meant by turbo alternators?
what is the effect of higher value of GD???
Why to keep capacitor bank off while generator running.
what is physical distance of isolator to VCB in 33/11kv sub stations
What is the basic principle of operation of alternators/dc generators?
i am venkat i got gre 930(verbal 270 quanta 660) and my toefl score 105..here question is why u got less score in gre ? what i supposed to tell...any chance of rejection is there...my accadamics record is very good
An impedance of 100 ohms resistance and an unknown inductance is connected across the capacitor. The resulting impedance is a pure resistance of 500 ohms ifω = 10^5 rad/sec. calculate the values of inductor and capacitor.